Plan Review Notes For Permit 15070293 |
Permit Number |
15070293 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-02 11:56:08 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. | | | | FBC 107.3.5.3 PROVIDE A CIRCUITING PLAN OR NOTES UPON | | THE PLAN TO DEMONSTRATE THE FOLLOWING. WIRE SIZE, | | WIRING METHOD, OCP. | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM, IF APPLICABLE. | | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | | NEC 210 - PROVIDE GFCI PROTECTED OUTLET ON BATHROOM. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | |
|