Plan Review Notes
Plan Review Notes For Permit 15070276
Permit Number 15070276
Review Stop G
Sequence Number 3
Notes
Date Text
2015-08-17 12:31:22GAS REVIEW - THE FOLLOWING DEFICIENCIES HAVE BEEN
 NOTED:
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS GAS WATER HEATER. THE APPLIANCE SHALL BE
 LISTED AND LABELED PER 2014 FBC-R SEC. G 2404.3.
 2) INDICATE THE DELIVERY PRESSURE OF THE GAS SYSTEM.
 2014 FBC-R SEC.G2413.2.
 3) INDICATE THE TYPE OF PIPING TO BE INSTALLED IN THE
 CEILING TO THE RANGE AND THE DRYER.WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 4) SUBMIT COMBUSTION AIR CALCCULATIONS FOR THE RANGE
 AND DRYER. 2014 FBC-R SEC.G2407.
 5) IF THIS IS A 1/2 LB PRESSURE SYSTEM, THE SYSTEM IS
 UNDERSIZED.THE APPLICABLE TABLE IS G2413.4 (1) AND THE
 LENGTH COLUMN TO BE USED FOR SIZING THE SYSTEM IS 40
 FEET.THE MAXIMUM BTU LOAD ON A 1" PIPE IS 320,000. THE
 MINIMUM SIZE FROM THE METER SHALL BE 1 1/4 INCHES
 (SEC.A) , THE SIZE TO THE TANKLESS WATER HEATER SHALL
 BE 1" (SEC. B) AND THE LINE SUPPLYING THE RANGE AND
 HEATER SHALL BE 3/4"(SEC.C).
  
 A NOTE CAN BE PLACED ON THE PLAN STATING THAT THE GAS
 WILL BE UNDER A SEPARATE PERMIT AND THE GAS DRAWING
 SHALL BE REMOVED FROM THE PLANS AND THEN I CAN APPROVE
 IT AS A SEPARATE PERMIT REQUIRED PROVISO.
  
  