2015-08-08 03:57:24GAS SHALL BE UNDER A SEPARATE PERMIT. THE FOLLOWING
 ITEMS NEED TO BE ADDRESSED WHEN THE GAS PERMIT
 APPLICATION IS SUBMITTED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER 20114 FBC -RESIDENTIAL SEC.G2404.3.
 2) INDICATE THE DELIVERY PSI OF THE GAS FOR THE SYSTEM.
 3) INDICATE THE APPLICABLE SIZING TABLES FROM CHAPTER
 24 OF THE 2014 FBC - RESIDENTIAL USED TO SIZE THE
 SYSTEM.
 4) INDICATE ON THE PLAN THE TYPE OF PIPE MATERIAL USED
 INSIDE THE STRUCTURE.
 5) THE SIZE OF THE GAS SUPPLY FROM THE METER MAY BE
 UNDERSIZED BASED ON THE BTU LOAD & THE TOTAL DISTANCE
 TO THE MOST REMOTE OUTLET. THIS WILL BE DETERMINED WHEN
 THE ADDITIONAL REQUESTED INFORMATION IS SUBMITTED. THE
 LINE MAY HAVE TO BE INCREASED TO 1 1/2 INCHES.THE
 ENTIRE SYSTEM MAY BE UNDERSIZED.
  