2015-07-17 14:16:34 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. THE USE OF THE ROOM IS NOT CLEAR. PLAN STATES THIS | | IS A "REPUMP ROOM." A FIRE RATED DOOR WITH A CLOSER IS | | PROPOSED. | | | | SEE FBC 1008.1.10: | | | | ELECTRICAL ROOMS WITH EQUI9PMENT RATED 1200 AMPERES OR | | MORE AND OVER 6 FEET WIDE THAT CONTAIN OVER-CURRENT | | DEVICES, SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT | | OR EXIT ACCESS DOORS SHALL BE EQUIPPED WITH PANIC | | HARDWARE OR FIRE EXIT HARDWARE. | | | | REVISE PLAN TO SHOW COMPLIANCE. | | | | 2. ON THE PLAN, PROVIDE THE PRINTED NAME AND SIGNATURE | | OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE PLAN, | | FBC 107. | | | | |
|