Plan Review Notes For Permit 15070178 |
Permit Number |
15070178 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-05 08:12:29 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15070178 | | MASTER: 14120580 | | ADD: 901 45TH ST. | | CONT: HEDRICK BROTHERS | | TEL: ( 561)718-9166 | | E-MAIL: | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: WED. AUGUST 05/2015 | | ACTION: DENIED | | | | 1) THE PRODUCT APPROVAL A MIAMI-DADE NOA 10-1202.01 | | NEITHER PAGE 3 OR 4 OF THE FASTENER TYPES HAS BEEN | | CIRCLED TO PROVIDE WHAT THE SLOPE IS, MOMENT DUE TO | | GRAVITY, OR THE TYPE OF FASTENER. | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR ROOF | | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION | | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE | | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING | | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE | | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT | | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE | | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE | | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE | | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION | | DOCUMENTS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|