2015-11-10 09:51:15PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  
 2) REVISE PLANS TO SHOW THE SUPPLY DUCT FROM THE AHU IN
 THE SECOND FLOOR ATTIC DOWN TO THE FIRST FLOOR CEILING.
 SPECIFY THE DUCT SIZE AND SHOW THE CHASE THAT WILL
 ENCLOSE THE DUCT. FBC 107.2.1
  
 3) THE ENERGY FORM 405 THAT WAS SUBMITTED IS THE 2010
 VERSION. SUBMIT THE 2014 VERSION OF FORM 405. 2014 FBC
 ENERGY CONSERVATION
  
 4) THE JURISDICTION NUMBER FOR WEST PALM BEACH IS
 604700, NOT 603800.
  