Plan Review Notes For Permit 15070145 |
Permit Number |
15070145 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-11-10 09:51:15 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR | | PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE | | CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS | | REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL | | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND | | COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND | | SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY | | TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC | | 61G15-23.002 AND FAC 61G15-23.003 | | | | 2) REVISE PLANS TO SHOW THE SUPPLY DUCT FROM THE AHU IN | | THE SECOND FLOOR ATTIC DOWN TO THE FIRST FLOOR CEILING. | | SPECIFY THE DUCT SIZE AND SHOW THE CHASE THAT WILL | | ENCLOSE THE DUCT. FBC 107.2.1 | | | | 3) THE ENERGY FORM 405 THAT WAS SUBMITTED IS THE 2010 | | VERSION. SUBMIT THE 2014 VERSION OF FORM 405. 2014 FBC | | ENERGY CONSERVATION | | | | 4) THE JURISDICTION NUMBER FOR WEST PALM BEACH IS | | 604700, NOT 603800. | | |
|