Plan Review Notes
Plan Review Notes For Permit 15070145
Permit Number 15070145
Review Stop E
Sequence Number 2
Notes
Date Text
2015-11-10 18:47:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved