2015-11-10 09:51:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  
 2) SHOW COMPLIANCE WITH FBC R401.3 FOR SURFACE
 DRAINAGE. SEE COMMENT #5 FROM FIRST REVIEW.
  
 3) PROVIDE A SECTIONAL GARAGE DOOR BUCK DETAIL.
 INDICATE THE SPECIFIC ANCHORS AND SPACING. FBC 107.2.1
 & FBC-R612.7.2
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 WAYNE DALTON GARAGE DOOR HAS DESIGN PRESSURES OF +30.0
 , -33.50 PSF AND THE PLANS REQUIRE +37.30, -45.70 PSF.
  
 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 THERMA TRU GLAZED OUTSWING STEEL DOOR FL7586.1 HAS
 DESIGN PRESSURES OF + 47.0, -47.0 PSF AND THE PLANS
 REQUIRE +41.24, -53.58 PSF.
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PEEL AND STICK ROOFING TILE UNDERLAYMENT
 AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1.
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ROOFING MATERIAL FOR THE GARAGE ROOF
 FLAT DECK AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1.
  
 8) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CEMENT ROOF TILE AND RESIST THE OVERTURN
 MOMENT. IF AN ADHESIVE IS USED, SUBMIT THE PRODUCT
 APPROVALS FOR IT. FBC 107.2.1 & FBC-R905.3
  
 9) R905.11.1 SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS
 SHALL HAVE A DESIGN SLOPE OF A MINIMUM OF ONE-FOURTH
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE)
 FOR DRAINAGE. (GARAGE) SPECIFY THE SLOPE ON THE PLANS.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  