2015-11-10 09:51:58 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR |
| PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE |
| CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS |
| REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL |
| SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND |
| COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND |
| SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY |
| TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC |
| 61G15-23.002 AND FAC 61G15-23.003 |
| |
| 2) SHOW COMPLIANCE WITH FBC R401.3 FOR SURFACE |
| DRAINAGE. SEE COMMENT #5 FROM FIRST REVIEW. |
| |
| 3) PROVIDE A SECTIONAL GARAGE DOOR BUCK DETAIL. |
| INDICATE THE SPECIFIC ANCHORS AND SPACING. FBC 107.2.1 |
| & FBC-R612.7.2 |
| |
| 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| WAYNE DALTON GARAGE DOOR HAS DESIGN PRESSURES OF +30.0 |
| , -33.50 PSF AND THE PLANS REQUIRE +37.30, -45.70 PSF. |
| |
| 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| THERMA TRU GLAZED OUTSWING STEEL DOOR FL7586.1 HAS |
| DESIGN PRESSURES OF + 47.0, -47.0 PSF AND THE PLANS |
| REQUIRE +41.24, -53.58 PSF. |
| |
| 6) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD FOR THE PEEL AND STICK ROOFING TILE UNDERLAYMENT |
| AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1. |
| |
| 7) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD FOR THE ROOFING MATERIAL FOR THE GARAGE ROOF |
| FLAT DECK AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1. |
| |
| 8) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| TO INSTALL THE CEMENT ROOF TILE AND RESIST THE OVERTURN |
| MOMENT. IF AN ADHESIVE IS USED, SUBMIT THE PRODUCT |
| APPROVALS FOR IT. FBC 107.2.1 & FBC-R905.3 |
| |
| 9) R905.11.1 SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS |
| SHALL HAVE A DESIGN SLOPE OF A MINIMUM OF ONE-FOURTH |
| UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) |
| FOR DRAINAGE. (GARAGE) SPECIFY THE SLOPE ON THE PLANS. |
| |
| 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |