Plan Review Notes
Plan Review Notes For Permit 15070144
Permit Number 15070144
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-29 07:32:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION 301.
  
 FOR FLORIDA STATE PRODUCT APPROVAL, PROVIDE THE
 FOLLOWING FOR EACH PRODUCT:
  
 COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE
 THE CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS,
 GENERAL INFORMATION ABOUT THE PRODUCT)
 EVALUATION REPORT
 INSTALLATION INSTRUCTIONS
  
 2. REVISE THE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS.
  
 3. IF ANY BEDROOM WINDOWS ARE LESS THAN 51" IN HEIGHT,
 REVISSE PLAN TO STATE THE TYPE OF EXIST WINDOW AND
 CLEAR OPENING SIZE, FBC R310, FBC EB 704.1. THE CLEAR
 OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
  
  