Plan Review Notes For Permit 15070113 |
Permit Number |
15070113 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-08 20:08:58 | ELECTRICAL PROVISOS FOR PERMIT 15070113: | | PER NEC 314.27 CEILING OR WALL OUTLET INTENDED FOR | | LUMINAIRE SHALL BE LISTED TO SUPPORT 50LB. | | PER NEC 210.52 D, YOU SHALL HAVE A GFCI OUTLET WITHIN | | 3FT. OF THE BATHROOM SINK. (SAME OR ADJACENT WALL) | | PER NEC 410.10D, LUMINAIRES DIRECTLY ABOVE SHOWER OR | | TUB SHALL BE LISTED FOR WET LOCATION | | PER NEC 404.2, UNLESS WORK IS IN CONDUIT WITH AMPLE | | SPARE ROOM, A NEUTRAL SHALL BE RUN TO EVERY SWITCH | | |
|