2015-07-08 08:27:24 | 7/8/2015 |
| PROJECT: FIRST BAPTIST CHURCH |
| PERMIT#: 15020847 |
| CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC |
| , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION, |
| FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW REVISION #15070084 |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) THERE ARE TWO RISER DIAGRAMS. NEITHER ONE IS CODE |
| COMPLIANT. MAKE SOME DELINEATION BETWEEN THE TWO IF |
| NECESSARY TO KEEP BOTH. IF ONE IS FOR REFERENCE PURPOSE |
| TO SHOW EXISTING AND ONE IS NEW THEN IDENTIFY THEM AS |
| SUCH SO IT IS CLEAR WHICH IS WHICH AND THE PURPOSE THEY |
| SERVE. |
| |
| 2) INDICATE ALL CONDUIT, WIRE, AND OCPD AND GROUNDING |
| SIZES AND TYPES. THERE ARE NO SIZES INDICATED FOR |
| CONDUITS, FEEDERS, GROUNDING ELECTRODE SYSTEM ETC... |
| THE WIRE SIZES THAT ARE SHOWN ARE NOT APPROVED FOR THE |
| OCPD INDICATED THAT THEY ARE CONNECTED TO. |
| |
| 3) PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS |
| AND SERVICE PROPOSED TO FEED THE LIGHT POLES. NEC 215.5 |
| |
| 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16. |
| |
| 6) PROVIDE MANUFACTURER PRODUCT INFORMATION |
| DOCUMENTATION FOR THE LIGHT FIXTURES PROPOSED |
| INDICATING OPERATING VOLTAGE AND LOAD AND COMPLIANCE |
| WITH NEC 110.3 |
| |
| 7) THE LIGHTING FIXTURE SCHEDULE INDICATES THE SITE |
| LIGHTING FIXTURES ARE DESIGNED TO OPERATE AT 120VOLTS. |
| HOWEVER THE SITE CIRCUITING PLAN AND PANEL SCHEDULE |
| INDICATE THE USE OF 2POLE BREAKERS OPERATING AT 208VOLT |
| TO FEED THE LIGHT FIXTURES DESIGNED TO OPERATE AT |
| 120VOLT. NEC 210.4(C) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |