2015-07-15 19:51:37PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU HAVE SUBMITTED A GENERIC DRAWING WITH MULTIPLE
 SYSTEMS. YOU SHALL INDICATE WHICH OF THESE SYSTEMS YOU
 WILL BE INSTALLING. IF YOUR INSTALLATION DIFFERS FROM
 THE SUBMITTED DRAWINGS, A SITE SPECIFIC DRAWING SHALL
 BE PROVIDED.
 2. YOU SHALL PROVIDE A SITE SPECIFIC RISER DIAGRAM
 SHOWING LOCATION OF INTERCONNECTION OF THE PV SYSTEM
 AND VARIOUS COMPONENTS. THIS RISER SHALL INCLUDE ALL
 REQUIRED SIGNAGE.
 3. THE SUBMITTED DRAWINGS APPEAR TO INCLUDE A BACK-FED
 BREAKER WITHOUT ANY REFERENCES TO THE REQUIREMENTS OF
 NEC 690.9(E).
 4. THE SUBMITTED SPECS FOR THE INVERTER FAIL TO
 INDICATE A LISTING OR RATING FOR AN INTER-ACTIVE SYSTEM
 AS REQUIRED IN NEC 690.60.
 5. FAILURE WITH NOTE 4 ABOVE VOIDS COMPLIANCE WITH NEC
 690.61.
 6. ROMEX, AS MENTIONED IN YOUR NOTES IS A BRAND NAME
 AND NOT A TYPE OF LISTED CABLE; FURTHERMORE NEC
 334.12(B)(4) PROHIBITS THE USE OF NM, NMC ETC. IN WET
 LOCATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  