2015-07-15 19:51:37 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| 1. YOU HAVE SUBMITTED A GENERIC DRAWING WITH MULTIPLE |
| SYSTEMS. YOU SHALL INDICATE WHICH OF THESE SYSTEMS YOU |
| WILL BE INSTALLING. IF YOUR INSTALLATION DIFFERS FROM |
| THE SUBMITTED DRAWINGS, A SITE SPECIFIC DRAWING SHALL |
| BE PROVIDED. |
| 2. YOU SHALL PROVIDE A SITE SPECIFIC RISER DIAGRAM |
| SHOWING LOCATION OF INTERCONNECTION OF THE PV SYSTEM |
| AND VARIOUS COMPONENTS. THIS RISER SHALL INCLUDE ALL |
| REQUIRED SIGNAGE. |
| 3. THE SUBMITTED DRAWINGS APPEAR TO INCLUDE A BACK-FED |
| BREAKER WITHOUT ANY REFERENCES TO THE REQUIREMENTS OF |
| NEC 690.9(E). |
| 4. THE SUBMITTED SPECS FOR THE INVERTER FAIL TO |
| INDICATE A LISTING OR RATING FOR AN INTER-ACTIVE SYSTEM |
| AS REQUIRED IN NEC 690.60. |
| 5. FAILURE WITH NOTE 4 ABOVE VOIDS COMPLIANCE WITH NEC |
| 690.61. |
| 6. ROMEX, AS MENTIONED IN YOUR NOTES IS A BRAND NAME |
| AND NOT A TYPE OF LISTED CABLE; FURTHERMORE NEC |
| 334.12(B)(4) PROHIBITS THE USE OF NM, NMC ETC. IN WET |
| LOCATIONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |