2015-07-27 10:45:451) SHT. CVR - GENERAL NOTE #1 - REFERS TO 2010 FBC.
 THIS PROJECT WAS SUBMITTED AFTER THE 5TH EDITION OF THE
 FBC WENT INTO EFFECT.REVISE THE NOTE TO FBC 5TH EDITION
 (2014).
 2) SHTS. A-2, A-3 & A-4 - PLUMBING FIXTURE REQUIREMENT
 TABLE - THE NUMBER OF "REQUIRED" WATER CLOSETS IS
 INCORRECT. TABLE 403.1 OF THE PLUMBING CODE REQUIRES
 ONE WATER CLOSET FOR EVERY 75 MALES AND EVERY 75
 FEMALES IN AN A-2 OCCUPANCY. THE OCCUPANT LOAD FOR EACH
 SEX EXCEEDS THIS AMOUNT. REVISE ALL THREE SHEETS TO
 SHOW THAT 2 WATER CLOSETS ARE REQUIRED FOR EACH SEX.
 3) SHTS. A-2, A-3 & A-3 - THE PLUMBING FIXTURE TABLE
 REFERS TO THE2004 CODE. REVISE THE NOTE TO READ FBC 5TH
 EDITION.
 4) A SERVICE SINK IS REQUIRED PER 5TH EDITION FBC-
 PLUMBING TABLE 403.1.
 5) WALLS IN THE TOILET ROOMS SHALL COMPLY WITH FBC
 1210.2.2 AND THE URINAL PARTITIONS SHALL COMPLY W/FBC
 1210.3.2. THE FINISH SCHEDULE ON THE PLANS SHOWS THE
 WALLS AS BEING PAINTED.
 6) SHTS. A-2, A-3, A-4 - INDICATE THE REQUIRED HANDICAP
 ACCESSIBLE URINAL ON THE PLANS AND SHOW THE REQUIRED 30
 INCH BY 48 INCH CCLEAR FLOOR SPACE REQUIRED FOR THE
 URINAL. 2014 FAC SECS. 213.3.3, 305.
 7) SHT. A-7 REFERS TO THE 2007 FLORIDA BUILDING CODE
 FOR ACCESSIBILITY MOUNTING REQUIREMENTS. THE HANDICAP
 CODE IN EFFECT IS THE 5TH EDITION (2014) OF THE FBC.
 REVISE NOTES AND REMOVE REFERENCE TO CHAPTER 11 AND
 2007 FBC.
 8) SHT. A-7 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE, NOT TO CENTER AS SHOWN.
 FBC-ACCESSIBILITY SEC. 609.4.
 9) SHT. A-7 - ACCESSIBLE BATHROOM STALL - SEVERAL OF
 THE ITEM IDENTIFICATION TAGS DO NOT CORRELATE WITH THE
 LIST OF ITEMS. CLARIFY. (SEE ITEMS T2,T3,T4, & T7 (NOT
 EVEN SHOWN) AND CIRCLED NUMBERS 2 & 3). CLARIFY.
 10) SHT. A-8 - APPLICABLE CODES TABLE - REVISE THE
 TABLE TO READ THE FLORIDA BUILDING CODE 5TH EDITION.
 11) SHTS. A-3 & A-4 ARE BOTH LABELED AS SECOND FLOOR
 PLANS. REVISE.
 12) SHT. A-4 - ROOM #304 (BEER COOLER) IS LABELED AS
 THE MEN'S RESTROOM. CORRECT THE PLANS.
 13) SHOW THE LENGTH & WIDTH OF THE STANDARD TOILET
 STALLS. COMPLY WITH FPC SEC.405.3.1.
 14) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. COMPLY WITH FPC SEC.1003.2, 1003.3.4,
 1003.3.4.1, 1003.3.4.2.
 15) SUBMIT A SITE PLAN OR SURVEY SHOWING WHERE THE NEW
 GREASE INTERCEPTORS WILL BE LOCATED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 16) SUBMIT A WATER RISER FOR ALL LEVELS FOR REVIEW. WPB
 AMENDMENTS TO FBC SEC. 107.3.5.1.3.
 17) SHT.P-1 - IDENTIFY THE AREA WHERE THE 2 " WATER
 LINE TO THE UPPER FLOORS IS LOCATED. IT APPEARS TO BE A
 SHAFT. INDICATE THE USE OF THE SHAFT ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 18) SHTS. P-1, P-2, P-3 - CLEARLY IDENTIFY THE COLD
 WATER LINES ON THE FLOOR PLANS. WPB AMEND. TO FBC SEC.
 107.2.1.
 19) THE HOT WATER SYSTEM SHALL COMPLY WITH FPC
 SEC.607.2 FOR THE REQUIRED HOT OR TEMPERED WATER TO THE
 FIXTURES.
 20) SUBMIT DETAILS FOR MEANS OF CONTROLLING THERMAL
 EXPANSION IN THE HOT WATER SYSTEM PER FPC SEC.607.3.
 21) SHT. P-3 - THE 1 1/2" WATER LINE FROM THE SECOND
 FLOOR APPEARS TO LOCATED IN THE MIDDLE OF THE FLOOR. -
 CLARIFY.
 22) SUBMIT A GAS RISER FOR REVIEW.SHOW THE LENGTH OF
 ALL CUT SECTIONS OF PIPE, WPB AMEND. TO FBC
 SEC.107.3.5.1.5.
 23) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES. CALCULATIONS SHALL COMPLY WITH THE 5TH
 RDITION OF FBC-FUEL GAS, SECTIONS 304.1, & 304.5
 THROUGH 304.11.
 24) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 APPLIANCES / EQUIPMENT.APPLIANCES/EQUIPMENT SHALL BE
 LISTED AND LABELED. FGC SEC.301.3.
 25) SHT. P-4 - REMOVE REFERENCE TO 2010 FUEL GAS CODE
 AND INSERT FUEL GAS CODE 5TH EDITION.
 26) SHT.P-4 - SIZING SUMMARY BOX - REMOVE THE REFERENCE
 TO THE 2010 FUEL GAS CODE AND INSERT FGC 5TH EDITION.
 27) SHT. P-4 - SIZE ALL SECTIONS OF THE SANITARY
 RISER.THERE ARE QUITE A FEW AREAS WHERE THERE IS NO
 PIPE SIZING. WPB AMEND. TO FBC SEC. 107.2.1.
 28) SHT.P-4 - THE URINALS REQUIRE VENTS. FPC SEC.901.2
 & 901.2.1.
 29) SHT. P-4 - IDENTIFY THE GREASY WASTE RISER FROM THE
 FIRST LEVEL TO THE THIRD LEVEL ON THE RISER DIAGRAM.
 WPB AMEND. TO FBC SEC. 107.2.1.
 30) SUBMIT A KITCHEN EQUIPMENT SCHEDULE.WPB AMEND. TO
 FBC SEC.107.3.5.1.3, 107.3.5.1.5.
 31) THE FLOOR DRAINS AND FLOOR SINKS ON ALL THREE
 LEVELS ARE NOT VENTED. COMPLY WITH 2014 FPC SEC.901.2 &
 901.2.1.
 32) SUBMIT DETAILS SHOWING THE TYPE, LOCATION,SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS CODE
 SECS. 502 THROUGH 505.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  