2015-07-27 10:45:45 | 1) SHT. CVR - GENERAL NOTE #1 - REFERS TO 2010 FBC. |
| THIS PROJECT WAS SUBMITTED AFTER THE 5TH EDITION OF THE |
| FBC WENT INTO EFFECT.REVISE THE NOTE TO FBC 5TH EDITION |
| (2014). |
| 2) SHTS. A-2, A-3 & A-4 - PLUMBING FIXTURE REQUIREMENT |
| TABLE - THE NUMBER OF "REQUIRED" WATER CLOSETS IS |
| INCORRECT. TABLE 403.1 OF THE PLUMBING CODE REQUIRES |
| ONE WATER CLOSET FOR EVERY 75 MALES AND EVERY 75 |
| FEMALES IN AN A-2 OCCUPANCY. THE OCCUPANT LOAD FOR EACH |
| SEX EXCEEDS THIS AMOUNT. REVISE ALL THREE SHEETS TO |
| SHOW THAT 2 WATER CLOSETS ARE REQUIRED FOR EACH SEX. |
| 3) SHTS. A-2, A-3 & A-3 - THE PLUMBING FIXTURE TABLE |
| REFERS TO THE2004 CODE. REVISE THE NOTE TO READ FBC 5TH |
| EDITION. |
| 4) A SERVICE SINK IS REQUIRED PER 5TH EDITION FBC- |
| PLUMBING TABLE 403.1. |
| 5) WALLS IN THE TOILET ROOMS SHALL COMPLY WITH FBC |
| 1210.2.2 AND THE URINAL PARTITIONS SHALL COMPLY W/FBC |
| 1210.3.2. THE FINISH SCHEDULE ON THE PLANS SHOWS THE |
| WALLS AS BEING PAINTED. |
| 6) SHTS. A-2, A-3, A-4 - INDICATE THE REQUIRED HANDICAP |
| ACCESSIBLE URINAL ON THE PLANS AND SHOW THE REQUIRED 30 |
| INCH BY 48 INCH CCLEAR FLOOR SPACE REQUIRED FOR THE |
| URINAL. 2014 FAC SECS. 213.3.3, 305. |
| 7) SHT. A-7 REFERS TO THE 2007 FLORIDA BUILDING CODE |
| FOR ACCESSIBILITY MOUNTING REQUIREMENTS. THE HANDICAP |
| CODE IN EFFECT IS THE 5TH EDITION (2014) OF THE FBC. |
| REVISE NOTES AND REMOVE REFERENCE TO CHAPTER 11 AND |
| 2007 FBC. |
| 8) SHT. A-7 - THE GRAB BARS SHALL BE MEASURED TO THE |
| TOP OF THE GRIPPING SURFACE, NOT TO CENTER AS SHOWN. |
| FBC-ACCESSIBILITY SEC. 609.4. |
| 9) SHT. A-7 - ACCESSIBLE BATHROOM STALL - SEVERAL OF |
| THE ITEM IDENTIFICATION TAGS DO NOT CORRELATE WITH THE |
| LIST OF ITEMS. CLARIFY. (SEE ITEMS T2,T3,T4, & T7 (NOT |
| EVEN SHOWN) AND CIRCLED NUMBERS 2 & 3). CLARIFY. |
| 10) SHT. A-8 - APPLICABLE CODES TABLE - REVISE THE |
| TABLE TO READ THE FLORIDA BUILDING CODE 5TH EDITION. |
| 11) SHTS. A-3 & A-4 ARE BOTH LABELED AS SECOND FLOOR |
| PLANS. REVISE. |
| 12) SHT. A-4 - ROOM #304 (BEER COOLER) IS LABELED AS |
| THE MEN'S RESTROOM. CORRECT THE PLANS. |
| 13) SHOW THE LENGTH & WIDTH OF THE STANDARD TOILET |
| STALLS. COMPLY WITH FPC SEC.405.3.1. |
| 14) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. COMPLY WITH FPC SEC.1003.2, 1003.3.4, |
| 1003.3.4.1, 1003.3.4.2. |
| 15) SUBMIT A SITE PLAN OR SURVEY SHOWING WHERE THE NEW |
| GREASE INTERCEPTORS WILL BE LOCATED. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 16) SUBMIT A WATER RISER FOR ALL LEVELS FOR REVIEW. WPB |
| AMENDMENTS TO FBC SEC. 107.3.5.1.3. |
| 17) SHT.P-1 - IDENTIFY THE AREA WHERE THE 2 " WATER |
| LINE TO THE UPPER FLOORS IS LOCATED. IT APPEARS TO BE A |
| SHAFT. INDICATE THE USE OF THE SHAFT ON THE PLANS. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 18) SHTS. P-1, P-2, P-3 - CLEARLY IDENTIFY THE COLD |
| WATER LINES ON THE FLOOR PLANS. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 19) THE HOT WATER SYSTEM SHALL COMPLY WITH FPC |
| SEC.607.2 FOR THE REQUIRED HOT OR TEMPERED WATER TO THE |
| FIXTURES. |
| 20) SUBMIT DETAILS FOR MEANS OF CONTROLLING THERMAL |
| EXPANSION IN THE HOT WATER SYSTEM PER FPC SEC.607.3. |
| 21) SHT. P-3 - THE 1 1/2" WATER LINE FROM THE SECOND |
| FLOOR APPEARS TO LOCATED IN THE MIDDLE OF THE FLOOR. - |
| CLARIFY. |
| 22) SUBMIT A GAS RISER FOR REVIEW.SHOW THE LENGTH OF |
| ALL CUT SECTIONS OF PIPE, WPB AMEND. TO FBC |
| SEC.107.3.5.1.5. |
| 23) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS |
| APPLIANCES. CALCULATIONS SHALL COMPLY WITH THE 5TH |
| RDITION OF FBC-FUEL GAS, SECTIONS 304.1, & 304.5 |
| THROUGH 304.11. |
| 24) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| APPLIANCES / EQUIPMENT.APPLIANCES/EQUIPMENT SHALL BE |
| LISTED AND LABELED. FGC SEC.301.3. |
| 25) SHT. P-4 - REMOVE REFERENCE TO 2010 FUEL GAS CODE |
| AND INSERT FUEL GAS CODE 5TH EDITION. |
| 26) SHT.P-4 - SIZING SUMMARY BOX - REMOVE THE REFERENCE |
| TO THE 2010 FUEL GAS CODE AND INSERT FGC 5TH EDITION. |
| 27) SHT. P-4 - SIZE ALL SECTIONS OF THE SANITARY |
| RISER.THERE ARE QUITE A FEW AREAS WHERE THERE IS NO |
| PIPE SIZING. WPB AMEND. TO FBC SEC. 107.2.1. |
| 28) SHT.P-4 - THE URINALS REQUIRE VENTS. FPC SEC.901.2 |
| & 901.2.1. |
| 29) SHT. P-4 - IDENTIFY THE GREASY WASTE RISER FROM THE |
| FIRST LEVEL TO THE THIRD LEVEL ON THE RISER DIAGRAM. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 30) SUBMIT A KITCHEN EQUIPMENT SCHEDULE.WPB AMEND. TO |
| FBC SEC.107.3.5.1.3, 107.3.5.1.5. |
| 31) THE FLOOR DRAINS AND FLOOR SINKS ON ALL THREE |
| LEVELS ARE NOT VENTED. COMPLY WITH 2014 FPC SEC.901.2 & |
| 901.2.1. |
| 32) SUBMIT DETAILS SHOWING THE TYPE, LOCATION,SIZE AND |
| TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS CODE |
| SECS. 502 THROUGH 505. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |