Plan Review Notes
Plan Review Notes For Permit 15061478
Permit Number 15061478
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-16 17:49:401ST REVIEW MECHANICAL: FBC-14 MECHANICAL
 PERMIT #15061478
 7/16/15
  
 1) THE OUTDOOR AIR CFM'S LISTED ON SHEET M-2 WERE NOT
 CALCULATED IN COMPLIANCE WITH TABLE 403.3 MECHANICAL AS
 INDICATED ON THE PLAN. THE OCCUPANT DENSITIES PER THE
 TABLE SHALL BE 70 PERSONS PER 1000 SF, OR THE ACTUAL
 OCCUPANT LOAD AS INDICATED ON SHEET A-8 CAN BE USED.
 PLEASE REVISE THE CALCULATIONS ACCORDINGLY.
 2) SHEET A-8: PLEASE REVIEW AND UPDATE THE APPLICABLE
 CODES TO THE FLORIDA BUILDING CODES FIFTH EDITION 2014.
 3) M-2: THE O/A BALANCE CALCULATION IS INCOMPLETE:
 PROVIDE THE TOTAL CFM'S AND INDICATE EITHER A POSITIVE
 OR NEGATIVE RESULT. PLEASE NOTE THAT THE CALCULATION
 WILL CHANGE DUE TO ADDITIONAL REQUIRED TOILET ROOM
 EXHAUST ADDED AT 50 CFM PER TOILET OR URINAL- TABLE
 403.3.
 4) ENERGY CALCULATIONS ARE REQUIRED PER SECTION 811.1
 FBC-14 EXISTING BUILDING, AND SECTION C101.4.3 FBC-10
 ENERGY CONSERVATION. REFERENCE SECTION C101.5.1 AND
 SUBMIT THE REQUIRED COMPLIANCE FORMS.
 5) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- REFER TO SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 6) M-2 : PROVIDE COMPLETE EQUIPMENT SCHEDULES ON THE
 PLANS FOR THE TRANE AC SYSTEMS 1 & 2 THAT LIST COOLING
 AND HEATING CAPACITIES BOTH SENSIBLE AND LATENT,
 REFRIGERANT TYPE, ELECTRICAL DATA, EFFICIENCY RATINGS,
 EXTERNAL STATIC PRESSURE, FAN AND COMPRESSOR DATA ETC.
 PROVIDE THE SAME FOR THE MINI-SPLITS SYSTEMS
 CONDITIONING THE THIRD FLOOR TOILET ROOMS AND ALSO
 INCLUDE THE MAKES AND MODELS OF THE EQUIPMENT.
 7) REVISE THE HVAC DESIGN REQUIREMENTS TO INDICATE DUCT
 SMOKE DETECTORS ARE REQUIRED FOR BOTH AC SYSTEMS. A)
 PROVIDE A SYMBOL TO SHOW THE LOCATIONS OF THE DEVICES
 ON SHEET M-1- SEE SECTION 606.2.1 FBC-10 MECHANICAL. B)
 PROVIDE AN INSTALLATION DETAIL FOR THE DEVICES ON THE
 PLAN, AND SUBMIT MANUFACTURER'S SPECIFICATIONS REVIEWED
 AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. C)
 INDICATE HOW THE DETECTORS WILL BE SUPERVISED IN
 ACCORDANCE WITH SECTION 606.4.1. PLEASE NOTE THAT THE
 FIRE DEPARTMENT REVIEW IS INDICATING A FIRE ALARM
 SYSTEM IS REQUIRED'
 8) M-1: GROUND FLOOR PLAN: THE 36X18 INCH MAIN RETURN
 GRILL IS UNDERSIZED FOR A 4000 CFM AIR FLOW- REFER TO
 SECTION 601.5. TYPICALLY, THE GRILL WOULD BE SIZED AT
 50 SQ. INCHES PER 100 CFM WHICH WOULD REQUIRES A GRILL
 WITH AN AIRFLOW AREA OF 2000 SQ. INCHES. ENLARGE THE
 GRILL SIZE ACCODINGLY.
 9) M-1: SECOND FLOOR: THE 22X16 INCH. MAIN RETURN GRILL
 IS UNDERSIZED FOR 2500 CFM. FOR 2500 CFM'S A 1250 SQ.
 IN. OF AIR FLOW AREA IS REQUIRED. ENLARGE THE GRILL
 ACCORDINGLY.
 10) M-1: GROUND FLOOR: RETURN DUCT CONNECTIONS ARE NOT
 SHOWN FOR THE TWO RETURN GRILLS IN THE TOILET ROOMS,
 AND THE R/A GRILL IN THE PRE-WASH AREA.
 11) M-1: GROUND AND SECOND FLOOR: SHOW THE TOILET ROOM
 EXHAUST DUCT RUNS, DUCT SIZES, AND TERMINATION
 LOCATIONS.
 12) M-1 AND M-3: THE 50 CFM EXHAUST FANS ARE UNDERSIZED
 FOR THE TOILET ROOMS- REFER TO TABLE 403.3: 50 CFM PER
 TOILET OR URINAL REQUIRED: PLEASE CORRECT.
 13) M-1: PROVIDE A CALCULATION TO VERIFY THE RETURN AIR
 FROM THE TOILET ROOMS CAN BE RECIRCULATED- REFER TO
 TABLE 403.3 FOOTNOTE G.
 14) SHOW THE LOCATIONS OF THE AC CONDENSERS, AND
 PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR INSTALLATION
 OF THE EQUIPMENT- SECTION 301.12.
 15) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF ALL
 EXHAUST OUTLETS AND AIR INTAKES WITH CLEARANCE DISTANCE
 MEASUREMENTS INDICATING COMPLIANCE WITH SECTIONS 401.4
 & 501.3.1
 16) PLACE A NOTE ON THE PLANS INDICATING SEPARATE
 PERMITS WILL BE PROVIDED FOR THE KITCHEN EXHAUST HOODS
 AND FIRE SUPPRESSION, AND FOR THE WALK IN COOLER.
  
  