Plan Review Notes For Permit 15061478 |
Permit Number |
15061478 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-28 11:06:35 | GAS | | 1) SUBMIT A GAS RISER FOR REVIEW.SHOW THE LENGTH OF ALL | | CUT SECTIONS OF PIPE, WPB AMEND. TO FBC | | SEC.107.3.5.1.5. | | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS | | APPLIANCES. CALCULATIONS SHALL COMPLY WITH THE 5TH | | RDITION OF FBC-FUEL GAS, SECTIONS 304.1, & 304.5 | | THROUGH 304.11. | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS | | APPLIANCES / EQUIPMENT.APPLIANCES/EQUIPMENT SHALL BE | | LISTED AND LABELED. FGC SEC.301.3. | | 4) SHT. P-4 - REMOVE REFERENCE TO 2010 FUEL GAS CODE | | AND INSERT FUEL GAS CODE 5TH EDITION. | | 5) SHT.P-4 - SIZING SUMMARY BOX - REMOVE THE REFERENCE | | TO THE 2010 FUEL GAS CODE AND INSERT FGC 5TH EDITION. | | 6) SUBMIT DETAILS SHOWING THE TYPE, LOCATION,SIZE AND | | TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS CODE | | SECS. 502 THROUGH 505. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|