Plan Review Notes
Plan Review Notes For Permit 15061478
Permit Number 15061478
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-07-08 08:46:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A-4 IS MISSED LABELED AS SECOND FLOOR.
  
 2) SHEET A-8 INDICATES INCORRECT CODE REFERENCES. THE
 PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH
 EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE
 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 3) THE BUILDING IS REQUIRED TO HAVE A MONOTORED FIRE
 SPRINKLER SYSTEM PER NFPA 101, CHAPTER 12, NEW ASSEMBLY
 OCCUPANCIES, 12.3.5. CONCEPTUAL DRAWING SHALL BE
 SUBMIITED WITH THIS PERMIT AND SHOP DRAWINGS SHALL
 FOLLOW.
  
 4) THE BUILDING IS REQUIRED TO HAVE A COMPLETE FIRE
 ALARM SYSTEM PER NFPA 101, CHAPTER 12, NEW ASSEMBLY
 OCCUPANCIES, 12.3.4. CONCEPTUAL DRAWING SHALL BE
 SUBMIITED WITH THIS PERMIT AND SHOP DRAWINGS SHALL
 FOLLOW.
  
 5) SHEET A-3 & A-9 SHOW 2 EXIT ACCESS DOORS THAT ARE
 TOO CLOSE TO EACH OTHER. EXITS SHALL BE REMOTELY
 LOCATED FROM EACH OTHER PER NFPA 101, CHAPTER 7 MEANS
 OF EGRESS, 7.4.
  
 6) IS THE STAIR NEW OF EXISTING? THERE IS NO STAIR
 DETAIL. PROVIDE ALL DETAIL PER CHAPTER 7 , 7.2.2..
 INCLUDING ACCESSIBILITY AND AREA OF REFUGE. THE STAIR
 SHALL LEAD TO A PUBLIC WAY; UNABLE TO DETERMINE THE
 PUBLIC WAY. UNABLE TO DETERMINE STAIRS DIMENSIONS,
 CONSTRUCTION MATERIAL.
  
 7) PROVIDE THE TOTAL EXIT TRAVEL DISTANCE FROM THE 3RD
 FLOOR ALONG THE UNPROTECTED OUTSIDE STAIR TO THE BOTTOM
 TREAD, MEETING THE REQUIREMENTS PER CHAPTER 12, 12.2.6
  
 8) THERE IS NO LIGHTING ON THE EXIT STAIR.
  
 9) IS THE STAIR APPROVED TO BE IN THE ALLEY?
  
 10) PROVIDE EXIT STAIR SEPARATION PER CHAPTER 7,
 7.2.2.6.3
  
 11) PROTECTION OF OPENINGS UNDER THE STAIR SHALL MEET
 CHAPTER 7, 7.2.2.6.4
  
 12) THE ELEVATOR SHALL COMPLY WITH NFPA 1, CHAPTER 11,
 BUILDING SERVICES,11.3
  
 13) SHEET A-8 SHOWS TWO EXIT ACCESSES PASSING THROUGH A
 "PREP/KITCHEN". PER CHAPTER 7, 7.5.2 EXITS SHALL NOT
 PASS THROUGH KITCHENS.
  
 14) SHEET A-10 SHOWS THE WORDS "FIRE SHUTTER" OVER A
 WINDOW OPENINGS. PLEASE EXPLAIN THE FUNCTION AND
 PURPOSE OF THESE.
  
 15) FURTHER COMMENT MAY BE PROVIDED ON THE SUBMIITAL
 AND REVIEW OF THE ABOVE.
  
  
  