Plan Review Notes
Plan Review Notes For Permit 15061472
Permit Number 15061472
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-22 10:50:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061472
 ADD: 930 MALCOLM CHANDLER LN.
 CONT: KAST
 TEL: (561)346-4994
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 22/ 2015
 ACTION: DENIED
  
 1) THIS UNIT HAS NOT BEEN ADDRESSED AS TO SUITE NUMBER
 JUST THE BUILDING ADDRESS. 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK.
  
 2) THE DESIGNER OF RECORD HAS NOT DECLARED TO WHAT
 PLANS THIS PROJECT IS BEING DESIGNED TO. PLEASE NOTE
 THE PLANS WERE SUBMITTED JUNE 30/ 2015 THE FIRST DAY OF
 THE ADOPTED 2014 5TH EDITION OF THE FLORIDA BUILDING
 CODE AND EXISTING BUILDING CODE. PLEASE REFER TO THE
 2014 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF
 OCCUPANCY SECTION 1001.3.1 FOR BUILDINGS WITH A PARTIAL
 CHANGE OF OCCUPANCY. "BUSINESS OCCUPANCY".
  
 3) SHEET A201 SHOWS A NEW MATER BATH DETAIL # 4/ A201.
 THIS DETAIL SHOWS THE EXTERIOR WALL OF THE RESTROOM
 WITH A 3'-6" GRAB BAR BUT IT APPEARS TO ONLY BE SECURED
 AT TWO POINTS, THERE IS WHAT APPEARS TO BE 1/2 OF THE
 GRAB BAR FLOATING IN MID-AIR. PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-ACCESSIBILITY 609.8 ALLOWABLE STRESSES
 SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A
 VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS (1112 N) IS
 APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 4) PLEASE REVIEW SHEET A201 OFFICE # 2, THE ENTRY DOOR
 INTO THE OFFICE DOES NOT HAVE THE 18 INCHES ON THE
 LATCH SIDE OF THE DOOR AS REQUIRED BY 2014
 FBC-ACESSIBLITY CODE 404.2.4 MANEUVERING CLEARANCES &
 TABLE 404.2.4.1.
  
 5) SHEET A201 IS NOW A OFFICE AND WILL NEED TO SHOW
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE SECTION
 606.1-5.
  
 6) THIS UNIT IS NOW CONSIDERED A COMMERICIAL OR
 BUSINESS OFFICE. PLEASE REVIEW 2014 FBC-B 903.3
 EXCEPTION REQUIREMENT FOR EXHAUST HOODS PROTECTED WITH
 A FIRE-EXTINGUISHING SYSSTEM IN ACCORDANCE WITH SECTION
 904.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  