2015-07-14 12:11:08 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15061471 |
| ADD: 6208 GEORGIA AVE. |
| CONT: TBD |
| TEL: (561)585-9211 |
| E-MAIL: [email protected] |
| |
| 2014 FBC-B / 5TH EDITION OF THE FLORIDA BUILDING CODE |
| 2014 EXISTING BUILDING CODE LEVEL II 801.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JULY 14/ 2015 |
| ACTION: DENIED |
| |
| 1) THIS PERMIT CAME IN AS A OWNER/ BUILDER PERMIT. THE |
| PERMIT APPLICATION AS OWNER LIST A GEORGIA AVE PB LLC |
| AS OWNER AND AUDRIA QUIST. ON THE OWNER/ BUILDER FORM |
| THE OWNER IS LISTED AS CHAD QUIST. PLEASE NOTE THE P. |
| B. C. PROPERTY APPRAISERS OFFICE SHOWS THE PROPERTY |
| SOLD LAST JUNE/ 2014 TO A GEORGIA AVE P B LLC. IF THE |
| CURRENT OWNER HAS BOUGHT IT SINCE THEN THEY WILL NEED |
| TO SUBMIT DOCUMENTATION THAT THEY ARE THE CURRENT |
| OWNERS. A CORPORATION, OR A LLC CAN NOT PULL PERMITS |
| SINCE THEY AS A OWNER CAN NOT APPEAR AS A INDIVIDUAL. |
| FL. S. 489.103. THE OTHER ISSUE THIS IS A 2 STORY |
| COMMERCIAL BUILDING WITH 2 OFFICES UPSTAIRS THAT HAVE |
| PULLED SEPARATE OCCUPATIONAL LICENSES |
| (BUSINESS TAX). OWNER /BUILDERS CAN NOT RENT OR LEASE |
| OUT THE PROPERTY UNDER A OWNER BUILDER PERMIT. |
| |
| 2) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010 |
| FBC. THE FIFTHED EDITION OF THE FLORIDA BUILDING CODE |
| (2014) WAS ADOPTED AND IN AFFECT STATE WIDE ON JUNE 30/ |
| 2015, THE SAME DAY THESE PLANS WERE SUBMITTED. PLEASE |
| REVISE TO THE CURRENT EDITION OF THE FBC 2014 EDITION. |
| |
| 3) PLEASE NOTE THE PLANS INDICATE WORK IS ONLY BEING |
| COMPLETED ON THE 1ST FLOOR. SHEET 1.1 INDICATES |
| EXISTING / PROPOSED. PLEASE PROVIDE A EXISTING FLOOR |
| PLAN AND A PROPOSED FLOOR PLAN OF THE 1ST FLOOR. |
| 107.3.5.1.1.1 COMMERCIAL BUILDINGS. FLOOR PLANS. |
| |
| 4) PLEASE PROVIDE COMPLIANCE WITH THE 2014 EXISTING |
| BUILDING CODE 806.1 A BUILDING OR ELEMENT THAT IS |
| ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| BUILDING CODE. 2014 FL. ACCESSIBLITY CODE 202.4.1 |
| DISPROPORTIONATE COST, PLEASE SHOW WHERE 20% OF THE |
| CONTRACT VALUE WILL BE SPENT IN ACCESSIBLE UPGRADES IN |
| THE ORDER STATED IN 202.4.1. |
| 4A) PLEASE SHOW COMPLIANCE WITH AN ACCESSIBLE ENTRANCE. |
| 2014 FL ACCESSIBILITY CODE206.2.4 SPACES & ELEMENTS & |
| 402.2 ACCESSIBLE ROUTES. |
| |
| 4B) THE RESTROOM AS SHOWN DOES NOT COMPLY WITH THE 2014 |
| FL ACCESSIBLITY CODE, SEE 604.3.2. |
| |
| 4C) THE BREAK ROOM SINK DOES NOT ALLOW FOR A SIDE NOR |
| FRONT APPROACH. SEE 2014 FL ACCESSIBILITY CODE 606.1-5. |
| |
| 5) SHEET 1.1 & 1.3 BOTH SHOW A DOORWAY BEING CHANGED |
| INTO A NEW WINDOW. PLEASE REVIEW THE 2014 FBC-B 1026.6 |
| REQUIRES THE EXTERIOR WALL TO BE A 1 HOUR FIRE RATING |
| BECAUSE OF THE EXTERIOR STAIRS. SHEET 1.1 SHOWS (2) |
| TENANTS ON THE 2ND FLOOR BOTH WITH ONLY (1) MEANS OF |
| EGRESS FOR BOTH. PLEASE NOTE THAT THE 2 STAIRS CAN ONLY |
| COUNT AS 1 SICNE THEY DO NOT END AT 1/2 THE DISTANCE |
| APART. |
| |
| 6) SHEET 1.1 & 1.3 THE DOORWAY ON THE EAST SIDE OF THE |
| BUILDING THAT IS BEING CHANGED INTO A WINDOW WILL NEED |
| TO BE EITHER IN COMPLIANCE WITH 2014 FBC-B 716.5 & |
| TABLE 716.5 OF 3/4 HR. THE NEW ENTRY DOOR AND SIDE |
| LIGHTS WILL ALSO NEED TO MEET THIS SAME REQUIREMENT |
| SINCE THEY ARE WITHIN 10'-0" OF THE STAIRS. |
| |
| 7) PLEASE ALSO NOTE THE 2 FIRE RATED OPENINGS WILL NEED |
| TO EITHER HAVE FIRE RATED GLAZING, THERE ARE VERY FEW |
| PRODUCTS THAT HAVE FIRE RATED GLAZING AND LARGE MISSILE |
| TESTED GLAZING UNITS. EITHER STORM SHUTTERS OR FIRE |
| SHUTTERS WILL BE REQUIRED. A FIRE SHUTTER CAN NOT BE |
| USED OVER THE ONLT MEANS OF EGRESS. FOR A FIRE SHUTTER |
| TO BE INSTALLED FOR THE NEW CORNER WINDOW IT WILL BE |
| REQUIRED TO BE ACTIVATED BY A FIRE ON THE INTERIOR OF |
| THE BUILDING. |
| |
| 8) SHEET 1.3 SHOWS THE NEW WINDOW TO HAVE PRESSURES OF |
| +44.5/ -48.3. FOR ZONE 5 FOR 20 SQ. FT. THE PRESSURES |
| FOR 170 MPH, VULT, EXPOSURE C, MEAN ROOF HEIGHT OF 20 |
| FT., |
| +38.6/ -50.4 VASD. THE NEGATIVE PRESSURES ARE LOW, FOR |
| WALL ZONE # 5 END ZONE. |
| |
| 9) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |