Plan Review Notes
Plan Review Notes For Permit 15061462
Permit Number 15061462
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-04 09:57:50BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061462
 ADD: 1500 CLARE AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. SEPT. 04/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 1A) NEW COMMENT, THERE IS A DISCREPANCY IN THE
 PLANS.SHEET B1. THE PLANS SHOW THE FLOOR LAYOUT OF 2
 NEW SPRAY BOOTHS AND A MIXING ROOM WHERE THERE IS
 ANOTHER DETAIL SHOWING A SINGLE SPRAY BOOTH AND MIXING
 ROOM ATTACHED. PLEASE REPRESENT THE ACTUAL LAYOUT NOT A
 GENERIC SHEET THAT COVERS ALL INSTALLATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 1B) SHEET B-2 SHOWS A FULLY ENCLOSED SPRAY BOOTH, THE
 GFS INSTALLATION & MAINTENANCE MANUAL IS FOR A
 DIFFERENT MODEL, A OPEN FACE BOOTH NOT MEETING THE
 REQUIREMENTS OF 2014 FBC-B 416.4 SPRAY BOOTHS. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 1C) ATTACHED AMEREX FIRE SUPRESSION SYSTEM IS FOR A
 PREVIOUS JOB. DATED 11/25/2013 (WHITED-OUT) NEW STICKER
 APPLIED DATED JUNE 23/ 2015 ADDRESS LOCATION 3076 SE
 DOMINICA TER. STUART, FL. 2010 FBC-B [F] 416.5 FIRE
 PROTECTION.
 AN AUTOMATIC SPRINKLER SYSTEM OR FIRE-EXTINGUISHING
 SYSTEM SHALL BE PROVIDED IN ALL SPRAY, DIP AND
 IMMERSING SPACES AND STORAGE ROOMS AND SHALL BE
 INSTALLED IN ACCORDANCE WITH CHAPTER 9.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
  
 COMMENT # 1 1ST REVIEW.THE PLAN LABELED B-1 SHOWS THE
 SPRAY BOOTH AGAINST THE EXTERIOR WALL. THE 2014 FBC-B
 416.4 SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND
 OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE. THE PLAN SHOWS THE SPRAY BOOTH AGAINST THE
 EXTERIOR WALLS.
 NFPA 33 5.3 REQUIRES THE SPRAY BOOTH TO BE A 1 HOUR
 CONSTRUCTION AND AT LEAST 3 FEET AWAY FROM THE EXTERIOR
 WALL. EXCEPTION # 2 WILL ALLOW THE UNIT TO BE CLOSER
 THAN 3 FT IF THE SPRAY BOOTH CAN BE MAINTAINED AND
 CLEANED. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR THE ONE HOUR FIRE RATING AS WELL AS
 SHOWING HOW THE UNIT WILL BE MAINTAINED AND KEPT CLEAN.
  
 2) COMPLIED. SHEET B-2 SHOWS A DETAIL WHERE CEILING
 JOIST/ RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT
 AND HEADERS ATTACHED. THE PLANS FAIL TO SHOW COMPLIANCE
 WITH 2014 FBC-B 2308.10.4.3 FRAMING AROUND HOLES.
 TRIMMERS AND HEADERS RAFTERS SHALL BE DOUBLED, OR OF
 LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF
 THE HEADER EXCEEDS 4 FEET. THE PLANS DO NOT INDICATE
 WHAT THE DOUBLE LINES REPRESENT, THE OUTER BAND IS PAST
 THE FRAMING MEMBER WHICH WILL REQUIRE THE FRAMING
 HEADER TO GO TO THE NEXT RAFTER. THE PLANS ALSO WILL
 NEED TO INDICATE THE TYPE OF HANGER/ BUCKET TO BE USED
 IN THIS INSTALATION FOR BOTH THE HEADER AND THE CUT
 RAFTERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  