2015-07-01 17:26:581ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061462
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 SPRAY BOOTH, THE MIXING ROOM, THE AIR FILTERS, THE
 EXHAUST FANS, THE COMPRESSOR AND THE SPRAY EQUIPMENT
 REVIEWED AND STAMPED BY THE ENGINEER OF RECORD-
 REFERENCE NFPA 33 SECTIONS (5.1.1), )5.1.4), (7.10.1),
 (8.3.2), (11.1), (12.1).
 2) THE LOCATIONS OF THE SPRAY BOOTHS SHOWN ABUTTING THE
 EXTERIOR CONCRETE WALLS DOES NOT LEAVE AMPLE SPACE FOR
 MAINTENANCE AS REQUIRED BY SECTION 5.3.2 EXCEPTION (2)
 NFPA 33.
 3) PROVIDE EXHAUST FAN SCHEDULES ON THE PLAN FOR THE
 BOOTHS AND THE MIXING ROOM- SECTION 7.10.1.
 4) PROVIDE AIR VELOCITY CALCULATIONS FOR EACH SPRAY
 BOOTH INDICATING COMPLIANCE WITH SECTION 502.7.3.3
 FBC-14 MECHANICAL.
 5) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 MIXING ROOM AND INDICATE HOW MAKE-UP AIR IS BEING
 PROVIDED. THERE IS NO LINK TO THE OVERHEAD DOOR SHOWN
 ON THE PLAN- SECTION 502.9.5.4 FBC-14 MECHANICAL.
 6) INDICATE HOW THE EXHAUST DUCTS ARE BEING SUPPORTED
 IN THE AREA BETWEEN THE TOP OF THE BOOTH AND THE ROOF
 LEVEL- SECTION 7.8 NFPA 33.
 7) REFERENCE SECTION 501.3.1(1) FBC-14 MECHANICAL AND
 PROVIDE A ROOF PLAN INDICATING THE REQUIRED MINIMUM
 CLEARANCE DISTANCES FOR EXHAUST TERMINATIONS TO
 PROPERTY LINES, AIR INTAKES, COMBUSTIBLE CONSTRUCTION,
 EXTERIOR WALLS, AND OPERABLE OPENINGS.
 8) INDICATE THE TYPE OF COMPRESSED AIR PIPING SUPPORTS
 OR HANGERS TO BE INSTALLED, AND SPACING OF THE HANGERS
 OR SUPPORTS.
 9) PROVIDE A THROUGH PENETRATION FIRE STOPPING METHOD
 FOR THE COMPRESSED AIR PIPING PENETRATING THE SPRAY
 BOOTHS
  