2015-07-27 14:54:20 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:15061462 |
| ADD: 1500 CLARE AVE. |
| CONT: FLORIDA FILTRATION |
| TEL: (561)582-5543 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 27/ 2015 |
| ACTION: DENIED |
| |
| 1) THE PLAN LABELED B-1 SHOWS THE SPRAY BOOTH AGAINST |
| THE EXTERIOR WALL. THE 2014 FBC-B 416.4 SPRAY BOOTHS |
| SHALL BE DESIGNED, CONSTRUCTED AND OPERATED IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THE |
| PLAN SHOWS THE SPRAY BOOTH AGAINST THE EXTERIOR WALLS. |
| NFPA 33 5.3 REQUIRES THE SPRAY BOOTH TO BE A 1 HOUR |
| CONSTRUCTION AND AT LEAST 3 FEET AWAY FROM THE EXTERIOR |
| WALL. EXCEPTION # 2 WILL ALLOW THE UNIT TO BE CLOSER |
| THAN 3 FT IF THE SPRAY BOOTH CAN BE MAINTAINED AND |
| CLEANED. PLEASE PROVIDE THE MANUFACTURERS |
| SPECIFICATIONS FOR THE ONE HOUR FIRE RATING AS WELL AS |
| SHOWING HOW THE UNIT WILL BE MAINTAINED AND KEPT CLEAN. |
| |
| 2) SHEET B-2 SHOWS A DETAIL WHERE CEILING JOIST/ |
| RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT AND |
| HEADERS ATTACHED. THE PLANS FAIL TO SHOW COMPLIANCE |
| WITH 2014 FBC-B 2308.10.4.3 FRAMING AROUND HOLES. |
| TRIMMERS AND HEADERS RAFTERS SHALL BE DOUBLED, OR OF |
| LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF |
| THE HEADER EXCEEDS 4 FEET. THE PLANS DO NOT INDICATE |
| WHAT THE DOUBLE LINES REPRESENT, THE OUTER BAND IS PAST |
| THE FRAMING MEMBER WHICH WILL REQUIRE THE FRAMING |
| HEADER TO GO TO THE NEXT RAFTER. THE PLANS ALSO WILL |
| NEED TO INDICATE THE TYPE OF HANGER/ BUCKET TO BE USED |
| IN THIS INSTALATION FOR BOTH THE HEADER AND THE CUT |
| RAFTERS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |