Plan Review Notes
Plan Review Notes For Permit 15061362
Permit Number 15061362
Review Stop Z
Sequence Number 1
Notes
Date Text
2015-07-30 17:37:58FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE CITYPLACE MANAGEMENT STAMP IS REQUIRED ON THE
 PLANS.
  
 2) THE GENERAL NOTE 3 ON SHEET M2.1 STATES THAT
 CONTRACTOR SHALL PLACE NEW CONDENSING UNITS ON ROOF.
 THERE IS NO ROOF PLAN OR OTHER SHEET WITH SHOWS NEW
 CONDENSING UNITS. WHAT NEW OR REPLACEMENT EQUIPMENT
 WILL BE PLACED ON THE ROOF? IF ANY NEW/REPLACEMENT
 MECHANICAL EQUIPMENT, TO INCLUDE HOODS, A/C, ETC. WILL
 BE INSTALLED ON THE ROOF, THEN A SHEET SHOWING HOW THE
 EQUIPMENT IS SCREENED IN ACCORDANCE WITH THE CITYPLACE
 REQUIREMENT SHALL BE PROVIDED.
  
 3) THE THEATER MAY ONLY BE FOR ACCESSORY USE TO THE
 OFFICE SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.