Plan Review Notes
Plan Review Notes For Permit 15061362
Permit Number 15061362
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-10 15:46:441ST REVIEW: FBC 2010 MECHANICAL, FBC-10 EXISTING
 BUILDING CODE
 PERMIT #15061362
 7/10/15
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 RE-CONFIGURED TENANT SPACES IN COMPLIANCE WITH SECTION
 709.1 FBC-10 EXISTING BUILDING CODE, AND TABLE 403.3
 FBC-10 MECHANICAL. PROVIDE A TABLE ON THE PLAN
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 2) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW HEAT PUMP SYSTEMS IN ACCORDANCE WITH ACCA
 MANUAL N OR THE ACCA/ASHRAE STANDARD 183- SECTION
 503.2.1 1 FBC-10 ENERGY CONSERVATION.
 3) SHEET M2.1: REFERENCE NOTE NUMBER SYMBOLS 4, 5, & 6
 ARE NOT SHOWN ON THE PLANS. IT APPEARS NOTE # 5 MAY NOT
 BE APPLICABLE TO THE PROJECT.
 4) M2.1: NOTE #2 INDICATES DISCHARGING THE THE FAN COIL
 UNIT CONDENSATE INTO PLUMBING DRAINS. PLEASE NOTE THAT
 UNCONTAMINATED COOLING WATER IS NOT PERMITTED TO DRAIN
 INTO THE CITY SANITARY SEWER PER SEC. 90-203 WPB CODE
 OF ORDINANCES. PROVISE AN APPROVED ALTERNATE LOCATION.
 5) M3.2: REMOVE THE RTU CURB DETAIL- IT IS NOT
 APPLICABLE TO THIS PROJECT. IN IT'S PLACE PLEASE
 PROVIDE ENGINEERED STRUCTURAL AND WIND LOAD TIE DOWN
 DETAILS FOR ANCHORING THE CONDENSER ROOF STANDS AND
 MOUNTING THE CONDENSERS TO THE STANDS- SECTION 301.12
 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  