Plan Review Notes For Permit 15061362 |
Permit Number |
15061362 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-23 19:38:41 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | 1. THE PLANS ARE TOO CLUTTERED FOR THE AMOUNT OF | | INFORMATION PROVIDED. | | 2. THE FLOOR PLAN DOES NOT INDICATE THE LOCATION OF THE | | TWO REQUIRED WATER COOLERS. | | 3. THE PANELS SCHEDULES DO NOT REFLECT THE CIRCUITS FOR | | THE TWO REQUIRED WATER COOLERS. | | 4. THE ELECTRIC WATER HEATER SHOWN ON SHEET P1, IS NOT | | SHOWN ON THE ELECTRICAL FLOOR PLANS NOR IN THE PANEL | | SCHEDULES. | | 5. ADDITIONAL DEFICIENCIES MAY BE NOTED WHEN PLANS ARE | | SUBMITTED IN PROPER SIZE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | |
|