Plan Review Notes For Permit 15061358 |
Permit Number |
15061358 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-07 19:39:27 | IMPORTANT NOTICE: | | THE DISTANCE FOR THIS SERVICE LATERAL IS NOT CLEARLY | | DEFINED AS PART OF THIS SUBMITTAL. THEREFORE BE ADVISED | | THAT FOR THE AMPERAGE OF 200 AMP USING 250KCMILS THWN-2 | | AL, THE MAXIMUM DISTANCE IS 122? FOR A 2% MAXIMUM OF 2% | | VOLTAGE DROP. | | ALL TRENCHING SHALL REMAIN OPEN FOR INSPECTION UNLESS | | PRIOR ARRANGEMENTS ARE MADE W/INSPECTOR. NO SITE TUBES | | ALLOWED | | |
|