Plan Review Notes For Permit 15061335 |
Permit Number |
15061335 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-25 09:06:39 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | RE-INSPECTION FEE(S). | | 1) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | BEDROOMS. THERE IS AN 8" DIA. SUPPLY DUCT TO THE MASTER | | BEDROOM AND BATH. IN ORDER TO PROVIDE THE REQUIRED | | 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY, THE | | TRANSFER DUCT IS REQUIRED TO HAVE A 10" DIAMETER. |
|