Date Text
2015-08-26 16:53:561ST REVIEW: FBC 2010
  
 PROVIDE ADDITIONAL DETAIL AND INFORMATION AS FOLLOWS:
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15, EQUIPMENT SCHEDULE AND INSTALLATION DETAILS AND
 CONDENSATION DETAILS TO DEMONSTRATE COMPLIANCE WITH
 FBCR MCHAPTER 13 AND FBCE CHAPTER 4..
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER