Plan Review Notes For Permit 15061326 |
Permit Number |
15061326 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-06 09:01:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATION, FBC | | R310, FBC EB 604.1. IF THIS IS LOCATED IN A SLEEPING | | ROOM, PROVIDE CLEAR OPENING DIMENSIONS. | | | | 2. THE PROPOSED WINDOW (+- 35PSF PER PRODUCT APPROVAL) | | DOES NOT MEET THE MINIMUM DESIGN PRESSURE REQUIRED. PER | | THE CONTRACTOR PROVIDED ENGINEERING, DESIGN PRESSURES | | FOR THIS OPENING ARE + 35.3, -38.5. | | | | 3. IMPACT PROTECTION REQUIRED, FBC 2010 RESIDENTIAL | | 301.2.1.2. THE PERMIT FOR THE ACCORDION SHUTTERS IS | | EXPIRED (10070015). | | | | | | | | | | | | |
|