Plan Review Notes For Permit 15061278 |
Permit Number |
15061278 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-08-14 04:21:31 | 1) SINCE THIS IS THE THIRD TIME THE PLANS HAVE BEEN | | REJECTED FOR THE SAME COMMENT REGARDING THE DRINKING | | FOUNTAIN, THE NEXT PLAN REVIEW SUBMITTAL IS SUBJECT TO | | BEING CHARGED 4 TIMES THE PLAN REVIEW FEE IN ACCORDANCE | | WITH FL. STATUTE 553.80. | | 2) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR | | SPACE PER 2010 FL. PLUMBING CODE TABLE 403.1. A MINIMUM | | OF 2 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE | | 2010 FAC AND FPC TABLE 403.1 FOOTNOTE (E). 3RD REQUEST. | | THE RESPONSE REGARDING ACCESS TO DRINKING WATER IN THE | | BREAK ROOM AND BUSINESS CENTER DOES NOT COMPLY WITH THE | | CODES. THE DRINKING FOUNTAIN FIXTURE IS REQUIRED IN THE | | NUMBER MANDATED BY THE CODE SECTIONS. SUBMIT REVISED | | SANITARY AND WATER RISERS THAT SHOW THESE FIXTURES. | | 3) GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL COMPLY | | WITH THE 2010 FAC SEC.609. SHT. SK 1.0 SHOWS THE GRAB | | BARS MEASURED TO THE CENTERLINE OF THE BAR. GRAB BARS | | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE | | FROM THE FINISH FLOOR IN ACCORDANCE WITH THE 2010 FAC | | SEC. 609. | | 4) SHT. SK 1.0 SHALL BEAR THE DIGITAL SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE | | WITH THE F.A.C. RULE 61G1-16.001, 61G1-16.005. THIS WAS | | OVERLOOKED IN THE PREVIOUS REVIEW. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805 PLUMBING PLAN REVIEW | | -6692 | | [email protected] | | | | |
|