Plan Review Notes
Plan Review Notes For Permit 15061278
Permit Number 15061278
Review Stop P
Sequence Number 4
Notes
Date Text
2016-08-14 04:21:311) SINCE THIS IS THE THIRD TIME THE PLANS HAVE BEEN
 REJECTED FOR THE SAME COMMENT REGARDING THE DRINKING
 FOUNTAIN, THE NEXT PLAN REVIEW SUBMITTAL IS SUBJECT TO
 BEING CHARGED 4 TIMES THE PLAN REVIEW FEE IN ACCORDANCE
 WITH FL. STATUTE 553.80.
 2) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR
 SPACE PER 2010 FL. PLUMBING CODE TABLE 403.1. A MINIMUM
 OF 2 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE
 2010 FAC AND FPC TABLE 403.1 FOOTNOTE (E). 3RD REQUEST.
 THE RESPONSE REGARDING ACCESS TO DRINKING WATER IN THE
 BREAK ROOM AND BUSINESS CENTER DOES NOT COMPLY WITH THE
 CODES. THE DRINKING FOUNTAIN FIXTURE IS REQUIRED IN THE
 NUMBER MANDATED BY THE CODE SECTIONS. SUBMIT REVISED
 SANITARY AND WATER RISERS THAT SHOW THESE FIXTURES.
 3) GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL COMPLY
 WITH THE 2010 FAC SEC.609. SHT. SK 1.0 SHOWS THE GRAB
 BARS MEASURED TO THE CENTERLINE OF THE BAR. GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 FROM THE FINISH FLOOR IN ACCORDANCE WITH THE 2010 FAC
 SEC. 609.
 4) SHT. SK 1.0 SHALL BEAR THE DIGITAL SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE
 WITH THE F.A.C. RULE 61G1-16.001, 61G1-16.005. THIS WAS
 OVERLOOKED IN THE PREVIOUS REVIEW.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  