Plan Review Notes For Permit 15061278 |
Permit Number |
15061278 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-04-19 09:21:50 | 1) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR | | SPACE PER 2010 FL. PLUMBING CODE TABLE 403.1. A MINIMUM | | OF 2 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE | | 2010 FAC AND FPC TABLE 403.1 FOOTNOTE (E). 2ND REQUEST. | | THE RESPONSE REGARDING ACCESS TO DRINKING WATER IN THE | | BREAK ROOM AND BUSINESS CENTER DOES NOT COMPLY WITH THE | | CODES. THE DRINKING FOUNTAIN FIXTURE IS REQUIRED IN THE | | NUMBER MANDATED BY THE CODE SECTIONS. SUBMIT REVISED | | SANITARY AND WATER RISERS THAT SHOW THESE FIXTURES. | | 2) TOILET ROOM #1152 - THE DOOR SWINGS INTO THE CLEAR | | FLOOR SPACE FOR THE LAVATORY. DOORS SHALL NOT SWING | | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE | | 2010 FBC-ACCESSIBILITY SEC.603.2.3.( SEE EXCEPTION | | #2).2ND REQUEST. | | 3) SHOW THE INSIDE CLEAR LENGTH AND WIDTH OF THE | | SHOWERS ON SHEET SK-1.0. COMPLY WITH SEC. 417.4 OF 2010 | | FPC AND SEC. 608 OF THE 2010 FAC. | | 4) THE SHOWER CONTROLS SHALL COMPLY WITH THE 2010 FAC | | SEC.608.5. SUBMIT DETAILS.FBC 107.1. | | 5) GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL COMPLY | | WITH THE 2010 FAC SEC.609. PROVIDE DETAILS. CLEARLY | | INDICATE THE ACCESSIBLE SHOWER ON THE PLANS OR ARE THEY | | ALL ACCESSIBLE? CLARIFY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|