2016-02-20 05:34:23 | 1) THE RESPONSE NARRATIVE STATES THAT THE 12TH FLOOR |
| HAS BEEN REMOVED FROM THE SCOPE OF WORK BUT THERE ARE |
| STILL PLANS FOR THE 12TH FLOOR BUILDOUT INCLUDED IN |
| THIS SUBMITTAL. CLARIFY. |
| 2) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE |
| GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO |
| THE TOP OF THE GRIPPING SURFACE PER THE 2010 |
| FBC-ACCESSIBILITY SEC. 609.4. |
| 3) SUBMIT THE OCCUPANT LOAD FOR THE 11TH LEVEL IN |
| ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1. |
| 4) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY |
| WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH |
| 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL |
| APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL |
| BE CENTERED ON THE APPLIANCE. |
| 5) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER |
| ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY |
| SECS.212.1, 606. |
| 6) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE |
| CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER |
| CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE |
| MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86 |
| INCHES ALLOWS FOR TOLERANCES. |
| 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS & |
| TOILET COMPARTMENTSL ON SHT.012 A1.03. COMPLY WITH 2010 |
| FBC-ACCESSIBILITY & PLUMBING VOLUMES. |
| 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET |
| COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY |
| WITH SEC.604.8.1. |
| 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL |
| COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4. |
| 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR |
| SPACE PER 2010 FL. PLUMBING CODE. A MINIMUM OF 2 |
| DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE 2010 |
| FAC. |
| 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010 |
| FBC-ACCESSIBILITY SEC.603.2.3. |
| 12) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC |
| SEC.708.3.4. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |