Plan Review Notes
Plan Review Notes For Permit 15061278
Permit Number 15061278
Review Stop M
Sequence Number 2
Notes
Date Text
2016-02-25 15:52:452ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061278
 2/25/16
  
 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 FOR THE NEW AHU/CU 11-20.
 2) SHEET M4.01: THE VENTILATION CALCULATIONS FOR THE
 LAUNDRY ROOMS IS NOT IN COMPLIANCE WITH TABLE 403.3.
 PLEASE REVIEW THE TABLE AND REVISE THE CALCULATIONS
 ACCORDINGLY.
 3) THE RESPONSE NARRATIVE FROM RGD CONSUILTING
 ENGINEERS IS INDICATING THAT THE SCOPE OF WORK FOR THE
 12TH FLOOR "HAS BEEN REMOVED FROM THE PROJECT", HOWEVER
 THE 12TH FLOOR PLAN SHEETS ARE STILL INCLUDED IN THE
 PLAN SETS. PLEASE CONTACT PLAN REVIEW LIBRARIAN
 CAROLINE PUELL OR LAURA MARCHANT AND HAVE ALL 12TH
 FLOOR PLAN SHEETS REMOVED.
 4) M2.02: THE EXHAUST GRILL IN THE WOMEN'S TOILET ROOM
 IS MISLABELED AS A SUPPLY DIFFUSER.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS
 WITH AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
 6) SUBMIT TWO COPIES OF THE NOA FOR THE ROOF STAND WITH
 AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER