2015-07-25 09:44:02 | 1) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE |
| GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO |
| THE TOP OF THE GRIPPING SURFACE PER THE 2010 |
| FBC-ACCESSIBILITY SEC. 609.4. |
| 2) SUBMIT THE OCCUPANT LOAD FOR EACH LEVEL IN |
| ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1. |
| 3) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY |
| WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH |
| 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL |
| APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL |
| BE CENTERED ON THE APPLIANCE. |
| 4) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER |
| ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY |
| SECS.212.1, 606. |
| 5) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE |
| CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER |
| CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE |
| MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86 |
| INCHES ALLOWS FOR TOLERANCES. |
| 6) SHT.012A1.04 - ROOMS 1212 & 1213 - A CLEARANCE OF 36 |
| INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM MEASURED |
| FROM THE CONTROL WALL SHALL BE PROVIDED PARALLEL TO THE |
| SHOWER ENTRANCES PER THE 2010 FBC-ACCESSIBILITY, |
| SEC.608.2.1. THE PLANS DO NOT SHOW THE CLEARANCE. |
| 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS, |
| TOILET COMPARTMENTS, & URINAL STALL ON SHT.012 A1.04. |
| COMPLY WITH 2010 FBC-ACCESSIBILITY & PLUMBING VOLUMES. |
| 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET |
| COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY |
| WITH SEC.604.8.1. |
| 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL |
| COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4. |
| 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH AND |
| 12TH FLOOR SPACES PER 2010 FL. PLUMBING CODE. A MINIMUM |
| OF 2 DRINKING FOUNTAINS ARE REQD. ON EACH FLOOR PER |
| SEC. 211.2 OF THE 2010 FAC. |
| 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010 |
| FBC-ACCESSIBILITY SEC.603.2.3. |
| 12) SHTS.070 P5.11 & 071 P5.12 - THE STACKS FOR THE |
| WASHING MACHINES SHALL BE A MINIMUM OF 3" PER THE 2010 |
| FPC SEC.406.3. |
| 13) BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH |
| SHALL BE INCREASED ONE PIPE SIZE FOR THE ENTIRE |
| DEVELOPED LENGTH OF THE VENT PIPE PER 2010 FPC |
| SEC.916.4.1.(SEE VENTS FOR TOILET ROOMS IN LOCKERS ON |
| LEVEL 12). |
| 14) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC |
| SEC.708.3.4. |
| |
| PLUMBING PLAN REVIEW |