Plan Review Notes
Plan Review Notes For Permit 15061278
Permit Number 15061278
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-25 09:44:021) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE
 GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2010
 FBC-ACCESSIBILITY SEC. 609.4.
 2) SUBMIT THE OCCUPANT LOAD FOR EACH LEVEL IN
 ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1.
 3) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY
 WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH
 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL
 APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE APPLIANCE.
 4) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER
 ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY
 SECS.212.1, 606.
 5) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE
 CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER
 CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE
 MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86
 INCHES ALLOWS FOR TOLERANCES.
 6) SHT.012A1.04 - ROOMS 1212 & 1213 - A CLEARANCE OF 36
 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM MEASURED
 FROM THE CONTROL WALL SHALL BE PROVIDED PARALLEL TO THE
 SHOWER ENTRANCES PER THE 2010 FBC-ACCESSIBILITY,
 SEC.608.2.1. THE PLANS DO NOT SHOW THE CLEARANCE.
 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS,
 TOILET COMPARTMENTS, & URINAL STALL ON SHT.012 A1.04.
 COMPLY WITH 2010 FBC-ACCESSIBILITY & PLUMBING VOLUMES.
 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET
 COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY
 WITH SEC.604.8.1.
 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL
 COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4.
 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH AND
 12TH FLOOR SPACES PER 2010 FL. PLUMBING CODE. A MINIMUM
 OF 2 DRINKING FOUNTAINS ARE REQD. ON EACH FLOOR PER
 SEC. 211.2 OF THE 2010 FAC.
 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010
 FBC-ACCESSIBILITY SEC.603.2.3.
 12) SHTS.070 P5.11 & 071 P5.12 - THE STACKS FOR THE
 WASHING MACHINES SHALL BE A MINIMUM OF 3" PER THE 2010
 FPC SEC.406.3.
 13) BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED ONE PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE PER 2010 FPC
 SEC.916.4.1.(SEE VENTS FOR TOILET ROOMS IN LOCKERS ON
 LEVEL 12).
 14) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC
 SEC.708.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  