2015-07-14 14:33:52 | 1ST REVIEW: FBC 2010 MECHANICAL |
| PERMIT #15061278 |
| 7/14/15 |
| |
| 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR |
| THE NEW AHU/CU 11-20 SYSTEM IN ACCORDANCE WITH ACCA |
| MANUAL N OR THE ACCA/ASHRAE STANDARD 183- REFERENCE |
| SECTION 503.2.1 FBC-10 ENERGY CONSERVATION. |
| 2) IN ACCORDANCE WITH SECTION 709.1 FBC-10 EXISTING |
| BUILDING, PROVIDE MINIMUM VENTILATION CALCULATIONS FOR |
| THE RECONGFIGURED ROOMS AND SPACES ON THE 11TH AND 12TH |
| FLOORS- REFERENCE TABLE 403.3 FBC-10 MECHANICAL. |
| PROVIDE A SCHEDULE ON THE PLAN INDICATING THE MINIMUM |
| REQUIRED CFM'S OF O/A OR EXHAUST, AND THE CFM'S |
| PROVIDED. REFERENCE SECTIONS 503.4.5.1 AND 503.4.5.2 |
| FBC-10 ENERGY CONSERVATION, AND ADD NOTES ON SHEET M6.1 |
| TO INDICATE VAV TERMINAL DEVICE COMPLIANCES REGARDING |
| O/A. |
| 3) NEW FIRE DAMPERS ARE SHOWN ON THE PLANS: PROVIDE AN |
| EQUIPMENT SCHEDULE ON THE PLAN LISTING THE MAKES AND |
| MODELS, FIRE-RESISTANCE RATINGS, AND HOW THEY WILL BE |
| ACTUATED- PROVIDE A SEQUENCE OF OPERATION, AND CLARIFY |
| IF ANY OTHER ALTERATIONS TO THE SMOKE CONTROL SYSTEM |
| ARE PROPOSED. |
| 4) THE 12TH FLOOR PLAN LAYOUT ON THE ARCHITECTURAL |
| DEMOLITION SHEET (A1.02) DOES NOT MATCH THE LAYOUT |
| SHOWN ON THE MECHANICAL DEMO SHEET (M2.0). |
| 5) SHEET M2.02: EXHAUST VENTILATION FOR THE TOILET |
| ROOMS IS REQUIRED. PLEASE PROVIDE THE DETAILS, EXHAUST |
| DUCT RUNS, AND EXHAUST FAN SCHEDULES ON THE PLANS- |
| TABLE 403.3 FBC-10 MECHANICAL. |
| 6) M2.04: EXHAUST VENTILATION FOR THE LOCKER/TOILET |
| ROOMS IS REQUIRED. PROVIDE THE DETAILS, DUCT RUNS, AND |
| FAN SCHEDULES ON THE PLAN. |
| 7) M2.02 & M2.04 PROVIDE MAKE-UP AIR FOR THE DRYERS- |
| REFERENCE SECTION 504.5 FBC-10 MECHANICAL. NOTE THERE |
| IS A DUCT DROP SHOWN AT THE FRONT OF THE 12TH FLOOR |
| DRYER CLOSET, HOWEVER DOOR 1117 ENCLOSING THE CLOSET IS |
| NOT LISTED AS A LOUVERED DOOR ON THE SCHEDULE ON SHEET |
| A6.01. PROVIDE THE TOTAL LENGTHS OF THE DRYER EXHAUST |
| DUCT RUNS IN COMPLIANCE WITH SECTION 504.6.4, AND |
| SUBMIT PRODUCT DATA CUTSHEETS FOR THE APPLIANCES. |
| 8) M5.02: THE DESIGN PROFESSIONAL OF RECORD SHALL |
| CERTIFY THAT THE CU WILL BE INSTALLED TO WITHSTAND 170 |
| MPH WIND LOADS AND PRESSURES- REFERENCE 301.12 FBC-10 |
| MECHANICAL. PROVIDE NOTES ON THE PLAN INDICATING |
| COMPLIANCE. |
| |