Plan Review Notes For Permit 15061278 |
Permit Number |
15061278 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-06 20:28:13 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER WAS UNABLE TO COMPLETE THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE CORRECTIONS NOTED. | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR A SECOND REVIEW: | | | | 1. SEPARATE PERMIT REQUIRED FOR FIRE ALARM | | INSTALLATION. THEREFORE DO NOT INCLUDE THE FIRE ALARM | | DEVICES ON THIS SHEET. | | 2. THESE PAGES ARE TOO CLUTTERED TO PROPERLY IDENTIFY | | THE DIFFERENT ROOMS. PROVIDE A SEPARATE SHEET FOR THE | | REFLECTED CEILING. | | 3. EMERGENCY STAIRS NEED TO BE IDENTIFIED TO ASCERTAIN | | PROPER LOCATION OF EXIT LIGHTING. | | 4. EMERGENCY LIGHTING IS NOT CLEARLY INDICATED | | ACCORDING TO THE LEGEND. | | 5. IN THE 12TH FLR. INDICATE THE AREA DIRECTLY ADJACENT | | TO YOUR SCOPE OF WORK WITH RESPECT TO THE EXITS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | |
|