2015-07-27 11:41:26 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT:15061278 |
| ADD: 777 S. FLAGLER DR. FLOORS: 11TH & 12TH |
| CONT: WOOLEMS INC. |
| TEL: (561)835-0401 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 27/ 2015 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION WILL NEED TO INCLUDE UNDER |
| THE DESCRIPTION OF WORK THE 11TH FLOOR AS WELL AS THE |
| 12TH FLOOR. 107,2,1,3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) SHEET 008-A0.07 THE 11TH FLOOR AT GRID LINE F-H & 8 |
| THE SET OF HORIZONTAL SLIDING DOORS FROM THE ELEVATOR |
| LOBBY TO RECEPTION AREA WILL NEED TO SHOW COMPLIANCE |
| WITH: 2010 FBC-B 1008.1.4.3 PLEASE ALSO BE AWARE OF |
| 1008.1.10 PANIC HARDWARE FOR ASSEMBLY OCCUPANCIES. IF |
| THIS DOOR IS TO HAVE ACCESS-CONTROLLED EGRESS THEN |
| 1008.1.4.4 WILL ALSO BE REQUIRED. |
| |
| 3) SHEET 001-A1.03 FLOOR LEVEL 11 BREAKROOM 1113 THE |
| BREAKROOM IS APPROXIMATELY 900 SQ. FT. WHICH WILL HAVE |
| A OCCUPANT LOAD OF 50 OR GREATER. 2010 FBC-B TABLE |
| 1004.1.1 900 SQ. FT./ 15 = 60 OCCUPANTS. PLEASE SEE |
| DOORS 1113A THEY SWING INTO THE ROOM. THE 2010 FBC-B |
| SECTION 1008.1.2 REQUIRES DOORS TO SWING IN THE |
| DIRECTION OF EGRESS TRAVEL WHENEVER THE OCCUPANT LOAD |
| OF 50 OR MORE. |
| |
| 4) SHEET 011-A1.03 PLEASE PROVIDE THE TOTAL SQ. FT. OF |
| AREA FOR THE TENANT SPACE THIS FLOOR AND ALSO PROVIDE |
| THE SQ. FOOTAGE FOR ROOMS 1113 THE BREAKROOM, |
| CONFERENCE ROOM 1102 & CONFERENCE ROOM 1103 . IF THEY |
| ARE OVER 10 % OF THE TENANT SPACE FLOOR AREA THIS WILL |
| BE CONSIDERED A MIXED OCCUPANCY FLOOR. THE DESIGNER OF |
| RECORD WILL NEED TO DECLARE THEN IF IT IS A SEPERATED |
| OCCUPANCY OR NON-SEPARATED OCCUPNCY. SEE FBC-B 508.2.4 |
| VERSES 508.3. |
| |
| 5) SHEET 011-A1.03 BOTH 2 HR RATED EXITS FAIL TO SHOW |
| THE 1 1/2 HR. FIRE RATED DOOR ON THE EXIT ENCLOSURE. |
| 2010 FBC-B TABLE 715.4. |
| |
| 6) SHEET 011-A1.03 SHOWS A SPIRAL STAIR FROM THE 11TH |
| FLOOR TO THE 12TH FLOOR. PLEASE PROVIDE A CUT SECTION |
| THROUGH THIS AREA PROVIDING DETAILS WITH 2010 FBC-B |
| 708.2 EXCEPTION 2.1 THE REQUIRED DRAFT CURTAIN AND |
| CLOSELY SPACED FIRE SPRINKLERS. |
| |
| 7) SHEET 011-A1.03 PLEASE PROVIDE SPECIFICATIONS FOR |
| THE SPIRAL STAIRCASE SIZE OF STAIRS, HEIGHT OF STAIRS, |
| HANRAIL AND GAURD-RAIL REQUIREMENTS. |
| 2010 FBC-B 1009.9, 1012 & 1013. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |