Plan Review Notes
Plan Review Notes For Permit 15061269
Permit Number 15061269
Review Stop E
Sequence Number 4
Notes
Date Text
2015-10-20 15:38:23BELOW ARE THE COMMENTS WITH REGARDS TO MY FINDINGS:
 PG. FA-2.1.1
 1. SEE CHANGEMARKS 1, 2 & 3.THOUGH YOU ARE EXEMPT FROM
 MANUAL PULL STATION DEVICES, THIS UNIT ON THE GROUND
 FLOOR SHOULD BE RELOCATED CLOSER TO THE EXIT AS MARKED.
 2. SEE CHANGEMARK 4. SMOKE DETECTOR PROTECTION INSIDE
 THE ELECTRICAL ROOM AS WELL AS THE EQUIPMENT ROOMS IS
 REQUIRED BY FBC, SECTION 907.2.18.1, AND IS A WISER
 CHOICE THAN RUNNING FIRE SPRINKLER IN THERE.
 3. SEE CHANGEMARK 5 ALL ELECTRICAL AND/OR EQUIPMENT
 ROOMS ARE NOT IDENTIFIED AS REQUIRED BY FBC SECTION
 907.1.2(1). SMOKE DETECTOR PROTECTION INSIDE THE
 ELECTRICAL AND/OR EQUIPMENT ROOMS AS REQUIRED BY FBC,
 SECTION 907.2.18.1 AND IS A WISER CHOICE THAN RUNNING
 FIRE SPRINKLER IN THERE. YOU SHALL SUBMIT
 MANUFACTURER?S DATA SHEETS ON ALL THE PROPOSED
 EQUIPMENT AND DEVICES BEING INSTALLED. AS PER FBC
 SECTION 907.1.2(10)
 PG. FA-2.1.2
 1. ALL ELECTRICAL AND/OR EQUIPMENT ROOMS ARE NOT
 IDENTIFIED AS REQUIRED BY FBC SECTION 907.1.2(1). SMOKE
 DETECTOR PROTECTION INSIDE THE ELECTRICAL AND/OR
 EQUIPMENT ROOMS AS REQUIRED BY FBC, SECTION 907.2.18.1
 AND IS A WISER CHOICE THAN RUNNING FIRE SPRINKLER IN
 THERE. YOU SHALL SUBMIT MANUFACTURER?S DATA SHEETS ON
 ALL THE PROPOSED EQUIPMENT AND DEVICES BEING INSTALLED.
 AS PER FBC SECTION 907.1.2(10)
 PG. FA-2.1.3
 1. SEE CHANGEMARKS 1, 2 & 3. SMOKE DETECTOR PROTECTION
 INSIDE THE ELECTRICAL AND/OR EQUIPMENT ROOMS AS
 REQUIRED BY FBC, SECTION 907.2.18.1 AND IS A WISER
 CHOICE THAN RUNNING FIRE SPRINKLER IN THERE.
 PG. FA-2.1.4, FA-2.1.5, FA-2.1.6, FA-2.1.7, FA-2.1.8,
 FA-2.1.9
 1. ALL ELECTRICAL AND/OR EQUIPMENT ROOMS ARE NOT
 IDENTIFIED AS REQUIRED BY FBC SECTION 907.1.2(1). SMOKE
 DETECTOR PROTECTION INSIDE THE ELECTRICAL AND/OR
 EQUIPMENT ROOMS AS REQUIRED BY FBC, SECTION 907.2.18.1
 AND IS A WISER CHOICE THAN RUNNING FIRE SPRINKLER IN
 THERE.
 PG. FA-3.1.1
 1. ACCORDING TO THIS RISER DIAGRAM THERE ARE SPEAKERS
 ON THE GRD. FLOOR. SYMBOL OF WHICH DOES NOT APPEAR ON
 THE LEGEND ON PG. FA-4.1.1
 2. NOT ALL SMOKE DETECTORS REFLECTED ON THE RISER
 DIAGRAM APPEAR ON THE GRD FLOOR PLAN
 PG. FA-4.1.1
 1. CONFLICTING SYMBOL IDENTIFIERS PLEASE CORRECT OR
 CLARIFY.
 2. IN THE INTEREST OF CONSISTENCY, PLEASE REVISE THE WP
 INDICATORS TO BE TYPICAL THROUGHOUT THE PLANS.
 3. THIS SHOULD READ, "COVERED TO PROTECT"
  
 IN ADDITION TO ALL OF THE ABOVE YOU SHALL PROVIDE THE
 REQUIRED VOLTAGE DROP CALCULATIONS FOR ALL WIRING ALONG
 WITH BATTERY CALCS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
  