Plan Review Notes
Plan Review Notes For Permit 15061269
Permit Number 15061269
Review Stop E
Sequence Number 2
Notes
Date Text
2015-08-26 13:41:25THIS REVIEW WAS STARTED ON 7/17/15. ON 8/4/15 I WENT
 BACK TO IT AND TODAY 8/26/15 I COMPLETED THE REVIEW.
 THE APPLICATION/REVIEW FAILED ELECTRICAL AS NOTED
 BELOW:
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 PAGE FA2.1.1
 1. THIS SHEET IS MISSING THE COMPLETE TITLE BLOCK
 2. THIS SHEET HAS NO F/A MARKINGS.
  
 PAGE FA2.1.2
 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 2. SAME AS CHANGE MARK 1 FOR VARIOUS LOCATIONS ON THIS
 PAGE.
 3. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL
 STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A
 PULL BOX UNDER 200FT.
 4. IDENTIFY/INCLUDE THE ?DD INSIDE THE SQUARE? SYMBOL
 ON YOUR LEGEND. DUCT DETECTOR?
  
 PAGE FA2.1.3 THROUGH FA2.1.8 APPEAR TO HAVE SIMILAR
 ISSUES. BASICALLY NO MANUAL INITIATION DEVICES APPEAR
 ON THE FLOOR PLANS.
 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 2. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 3. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 4. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 5. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 6. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL
 STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A
 PULL BOX UNDER 200FT.
 7. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 8. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM.
 9. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM.
  
 THERE APPEARS TO BE SMOKE BARRIER DOOR IN THE CORRIDORS
 W/O THE SMOKE DETECTORS AND OR DOOR HOLDER RELAYS. IF
 THE CORRIDORS ARE COMPARTMENTALIZED SHOW THE REQUIRED
 DEVICES.
  
 PAGES FA2.1.9 ROOF
 1. THIS PAGE IS LACKING THE MANUAL INITIATION DEVICES
 AS WELL.
 2. THERE ARE SYMBOLS NOT IDENTIFIED ON THE LEGEND.
  
 PAGES FA3.1.1.3.1.3 & FA3.1.1.3.1.5 RISER DIAGRAMS
 1. NOTHING SHOWN FOR THE GROUND FLOOR ON THE RISER
 DIAGRAM APPEARS ON THE CORRESPONDING PAGE.
 2. THE CONTINUATION OF THE RISER DIAGRAM, PROBABLY PAGE
 FA3.1.1.3.1.4 (THIRD TO FIFTH FLOORS) IS MISSING.
 3. THE CONTINUATION OF THE RISER DIAGRAM FOR THE
 SEVENTH FLOOR TO ROOF IS ALSO MISSING.
 4. THE ENTIRE RISER DIAGRAMS WILL HAVE TO BE RECREATED
 TO INCLUDE THE MISSING DEVICES ONCE ADDED TO PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  