2015-08-26 13:41:25 | THIS REVIEW WAS STARTED ON 7/17/15. ON 8/4/15 I WENT |
| BACK TO IT AND TODAY 8/26/15 I COMPLETED THE REVIEW. |
| THE APPLICATION/REVIEW FAILED ELECTRICAL AS NOTED |
| BELOW: |
| PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| |
| PAGE FA2.1.1 |
| 1. THIS SHEET IS MISSING THE COMPLETE TITLE BLOCK |
| 2. THIS SHEET HAS NO F/A MARKINGS. |
| |
| PAGE FA2.1.2 |
| 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 2. SAME AS CHANGE MARK 1 FOR VARIOUS LOCATIONS ON THIS |
| PAGE. |
| 3. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL |
| STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A |
| PULL BOX UNDER 200FT. |
| 4. IDENTIFY/INCLUDE THE ?DD INSIDE THE SQUARE? SYMBOL |
| ON YOUR LEGEND. DUCT DETECTOR? |
| |
| PAGE FA2.1.3 THROUGH FA2.1.8 APPEAR TO HAVE SIMILAR |
| ISSUES. BASICALLY NO MANUAL INITIATION DEVICES APPEAR |
| ON THE FLOOR PLANS. |
| 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 2. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 3. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 4. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 5. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 6. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL |
| STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A |
| PULL BOX UNDER 200FT. |
| 7. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| REQUIRED WITHIN 5' OF EXIT. |
| 8. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM. |
| 9. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM. |
| |
| THERE APPEARS TO BE SMOKE BARRIER DOOR IN THE CORRIDORS |
| W/O THE SMOKE DETECTORS AND OR DOOR HOLDER RELAYS. IF |
| THE CORRIDORS ARE COMPARTMENTALIZED SHOW THE REQUIRED |
| DEVICES. |
| |
| PAGES FA2.1.9 ROOF |
| 1. THIS PAGE IS LACKING THE MANUAL INITIATION DEVICES |
| AS WELL. |
| 2. THERE ARE SYMBOLS NOT IDENTIFIED ON THE LEGEND. |
| |
| PAGES FA3.1.1.3.1.3 & FA3.1.1.3.1.5 RISER DIAGRAMS |
| 1. NOTHING SHOWN FOR THE GROUND FLOOR ON THE RISER |
| DIAGRAM APPEARS ON THE CORRESPONDING PAGE. |
| 2. THE CONTINUATION OF THE RISER DIAGRAM, PROBABLY PAGE |
| FA3.1.1.3.1.4 (THIRD TO FIFTH FLOORS) IS MISSING. |
| 3. THE CONTINUATION OF THE RISER DIAGRAM FOR THE |
| SEVENTH FLOOR TO ROOF IS ALSO MISSING. |
| 4. THE ENTIRE RISER DIAGRAMS WILL HAVE TO BE RECREATED |
| TO INCLUDE THE MISSING DEVICES ONCE ADDED TO PLANS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU |
| |
2015-08-04 16:37:32 | REVIEW RESULTS PENDING RESPONSE FROM WES. |