Plan Review Notes For Permit 15061261 |
Permit Number |
15061261 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-01 11:38:37 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE SLOPE AND MEAN ROOF HEIGHT OF THE ROOF. | | FBC 107.2.1 | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES AND THE | | MAXIMUM DESIGN PRESSURE LISTED IN THE CERTAINTEED NOA | | #14-0224.03 WILL BE INSTALLED. FBC-R301.2.1 | | | | 3) THE PROJECT IS LOCATED IN A 170MPH WIND SPEED WITH | | EXPOSURE CATEGORY C. SUBMIT SIGNED AND SEALED RAS 117 | | ENHANCED FASTENING CALCULATIONS AS REQUIRED BY | | LIMITATION #7 ON PAGE 16 OF NOA #14-0224.03. FBC | | 107.2.1 |
|