Plan Review Notes
Plan Review Notes For Permit 15061222
Permit Number 15061222
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-14 12:08:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1ST REVIEW: TEST REPORTS FOR QUIETWALK UNDERLAYMENT,
 LAMINATE FLOORING WERE SUBMITTED
 2ND REVIEW: SPEC SHEETS FOR QUIETWALK SUBMITTED
  
 FROM PREVIOUS LIST:
  
 1. FBC 1207.2, THE ASSEMBLY TESTED USED AN 8" SLAB FOR
 THE STC TEST. PROVIDE THE SLAB THICKNESS FOR THIS
 PROJECT. IF THE SLAB IS NOT 8", ADDITIONAL INFORMATION
 WILL BE REQUIRED SUCH AS A TEST REPORT WHICH USES AN 6"
 SLAB (LIKE THE IIC TEST), A DESIGN PROFESSIONAL'S
 COMPARATIVE ANALYSIS, OR THE MANUFACTURER'S ANALYSIS
 (ON LETTERHEAD).
  
 2ND REVIEW, THIS WAS NOT PROVIDED. MORE SPEC SHEETS
 WERE PROVIDED. SLAB THICKNESS FOR THIS JOB NOT
 PROVIDED, ANALYSIS (OR TEST USING A 7" OR 6" SLAB) NOT
 PROVIDED.
  
 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3. TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
 FOR PERMIT ISSUANCE, FBC 107.
  
 NEW COMMENT:
  
 4. SPEC SHEETS ARE NOT ACCEPTABLE IN LIEU OF TEST
 REPORTS DUE TO GENERAL DISCREPANCIES.
  
  
  
  