Notes |
Date |
Text |
2015-06-25 18:45:24 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) TWO SETS OF REVISED PLANS ARE REQUIRED. FBC 107.1 | | | | 2) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE DESIGN IS REQUIRED ON THE PLANS. FBC 107.2.1 - | | INFORMATION ON CONSTRUCTION DOCUMENTS. ALL INFORMATION, | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN. | | | | 3) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING | | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | RECORDS MANAGEMENT. THE REVISED PLANS ARE TOO SMALL AND | | NOT CLEAR. CLEARLY SPECIFY ALL GRILL AND DUCT SIZES ON | | THE PLANS. | | |
|