Plan Review Notes
Plan Review Notes For Permit 15061178
Permit Number 15061178
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-29 14:29:56IMPORTANT NOTICE:
 ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES ARE ALLOWED.
 UNDERGROUND RACEWAY SHALL BE SEALED AS INDICATED BY NEC
 300.5 (G)
 INTER-SYSTEM BONDING TERMINAL AS PER NEC 250.94 IS
 REQUIRED.