Plan Review Notes For Permit 15061178 |
Permit Number |
15061178 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-29 14:29:56 | IMPORTANT NOTICE: | | ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS | | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL | | INSPECTOR. NO SITE TUBES ARE ALLOWED. | | UNDERGROUND RACEWAY SHALL BE SEALED AS INDICATED BY NEC | | 300.5 (G) | | INTER-SYSTEM BONDING TERMINAL AS PER NEC 250.94 IS | | REQUIRED. |
|