Plan Review Notes
Plan Review Notes For Permit 15061113
Permit Number 15061113
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-20 08:29:531) THE SHOWER REQUIRES A VENT PER FPC SEC.901.2.
 2) INDICATE ON THE PLAN WHAT THESE RESTROOMS SERVE. A
 URINAL IS BEING DELETED AND THIS MAY BE A REQUIRED
 FISTURE PERR TABLE 403.1. DELETING THIS FIXTURE MAY BE
 CREATING A VIOLATION OF THE PLUMBING CODE.
 3) MANUFACTURER'S SPECIFICATIONS FOR THE STEAM UNIT
 SHALL BE ONSITE FOR INSPECTION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  