2015-07-24 07:42:07 | 2ND REVIEW: FBC 2010 MECHANICAL |
| 7/24/15 |
| |
| 1) IN RESPONSE TO 1ST REVIEW COMMENT #5, ORBIT LABS HAS |
| SUBMITTED LETTERS INDICATING MINIMAL LEVELS OF |
| FLAMMABLE VAPORS, GAS, FUMES, MIST, AND DUSTS FROM THE |
| CHEMICAL PROCESSES WILL BE EXHAUSTED THROUGH THE NEW |
| CAPTURE HOOD SYSTEM. IN ORDER TO VERIFY COMPLIANCE WITH |
| SECTION 510.2 FBC-10 MECHANICAL (WHICH OUTLINES THE |
| PARAMETERS BY WHICH A HAZARDOUS EXHAUST SYSTEM IS |
| REQUIRED), AND IN ACCORDANCE WITH SECTION 502.8, PLEASE |
| SUBMIT MSDS SHEETS FOR THE CHEMICAL 2-PROPANOL, |
| METHANOL, AND NIOTROGEN. INDICATE ON THE PLANS THE |
| QUANTITIES OF EACH CHEMICAL BEING STORED IN THE |
| FACILITY, AND HOW THE CHEMICALS ARE BEING STORED- ROOM, |
| CLOSET, CABINET? THE ISSUE IS FURTHER EVIDENCE IS |
| REQUIRED TO DETERMINE AN ACCURATE OCCUPANCY |
| CLASSIFICATION FOR THE FACILITY, AND WHICH ASSOCIATED |
| CODE REQUIREMENTS MUST BE ENFORCED- REFER TO TABLE |
| 307.1(1) AND SECTION 414 FBC-10 BUILDING. |
| 2) THE PLAN INDICATES A MANUALLY OPERATED RHEOSTAT WILL |
| CONTROL THE EXHAUST FAN OPERATION- REFER TO SECTION |
| 502.8.1.1 ITEM 3 AND PROVIDE EVIDENCE AS NOTED IN |
| COMMENT #1 TO INDICATE CONTINUOUS OPERATION IS NOT |
| APPLICABLE. |
| 3) INDICATE ON THE PLAN THE TYPE OF AND GAGE OF EXHAUST |
| DUCT MATERIAL TO BE CONNECTED TO THE EXHAUST HOOD, AND |
| TO THE NITROGEN GENERATOR- REFER TO SECTION 510.8 |
| FBC-10 MECHANICAL. |
| 3) AS PREVIOUSLY REQUESTED, PROVIDE AN EQUIPMENT |
| SCHEDULE AND AN EQUIPMENT FLOOR PLAN LAYOUT. IDENTIFY |
| ALL EQUIPMENT ON THE PLAN AS EITHER NEW, EXISTING, OR |
| FUTURE. |
| 4) AS PREVIOUSLY REQUESTED, SUBMIT THE MIAMI-DADE NOA |
| FOR THE AC ROOF STAND. |
| 5) THE SUBMITTED ENERGY COMPLIANCE FORM DOES NOT |
| INCLUDE THE ENERGY EFFICIENCY COMPLIANCE SUMMARY PAGES: |
| 6) PLEASE NOTE THAT THE CITY OF WPB BUILDING DIVISION |
| REQUIRES ALL COMPLIANCE DOCUMENTS, NOA'S, PRODUCT CUT |
| SHEETS ETC. TO BE SUBMITTED IN DUPLICATE. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |