Plan Review Notes
Plan Review Notes For Permit 15061111
Permit Number 15061111
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-25 14:30:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE AC SIZING LOAD CALCULATIONS INDICATE 60775
 BTU/HR FOR MISCELLANEOUS: PLEASE PROVIDE MORE SPECIFIC
 INFORMATION. IS THIS LOAD BEING GENERATED BY EQUIPMENT-
 EITHER NEW OR EXISTING?
 2) SHEET S-1 AND THE STRUCTURAL CALCULATIONS INDICATE
 TWO NEW EXHAUST FANS, HOWEVER ONLY ONE IS NOTED AND
 SHOWN IN THE MECHANICAL PLANS: PLEASE CLARIFY.
 3) CLARIFY HOW MAKE-UP AIR IS BEING PROVIDED FOR THE
 EXHAUST HOOD- EXISTING OR NEW SUPPLY? PROVIDE NOTES AND
 CALCULATIONS, AND DRAWINGS FOR ALL NEW INSTALLATIONS.
 4) PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN
 IDENTIFYING ALL NEW AND EXISTING EQUIPMENT IN THE LAB,
 INCLUDING THE PIECE OF EQUIPMENT THAT IS REQUIRING THE
 EXHAUST HOOD.
 5) WHAT IS THE TYPE OF EXHAUST- REFERENCE SECTION
 501.2.1 FBC-10 MECH. FOR OUTLET LOCATIONS, AND 510.2
 FOR HAZARDOUS EXHAUST REQUIREMENTS.
 6) SHEET A-1 SHOWS THE NEW AC AND FAN EQUIPMENT WITHIN
 10 FT. OF THE ROOF EDGE WHICH REQUIRES EITHER A GUARD
 OR A MINIMUM 42' PARAPET WALL- SECTION 304.11.
 7) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN
 PROFESSIONAL OF RECORD THAT INCLUDES FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S, AND PRODUCT DATA
 SHEETS FOR ALL NEW COMPONENTS OF THE AC AND EXHAUST
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  