2015-07-15 13:52:58 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR ANOTHER REVIEW. | | 1. THE INCORRECT CODE IS QUOTED. YOU QUOTE NFPA 72 2002 | | EDITION IN ONE PLACE AND THEN THE 2007 EDITION ELSE | | WHERE. | | 2. PER NFPA 72 2007, SECTION 5.13.6, A PULL STATION IS | | REQUIRED WITHIN 5' OF AN EXIT AT EVERY FLOOR. THIS | | MEANS THE MEZZANINE LEVEL. | | 3. PER FBC EACH ROOM SHALL BE LABELED | | 4. PER FBC, DETAILS OF CEILING HEIGHT SHALL BE | | PROVIDED. | | 5. THOUGH THE VISUAL NOTIFICATION DEVICES APPEAR TO BE | | WELL PLACED, THIS CAN CHANGE WITH THE ARRANGEMENT OF | | SHELVING ETC. THIS SHALL BE DETERMINED AT THE FINAL | | INSPECTION. |
|