Plan Review Notes
Plan Review Notes For Permit 15061087
Permit Number 15061087
Review Stop G
Sequence Number 2
Notes
Date Text
2015-07-04 06:52:561) THE PIPING PLAN SHOWS UNDERGROUND GAS PIPING &
 SLEEVE TO TWO DRYERS. GAS PIPING IS PROHIBITED PER THE
 2010 FBC-R SEC. G2415.4. THE INSTALLATION OF GAS PIPNG
 BENEATH BUILDINGS IS PERMITTED WHEN THERE IS NO OTHER
 WAY TO INSTALL THE PIPING. SUBMIT A FLOOR PLAN SHOWING
 THE LOCATION OF ALL ALL GAS APPLIANCES IN RELATION TO
 THE GAS METER. THE DRYERS SHALL NOT BE PIPED UNDER THE
 SLAB UNLESS THAT IS THE ONLY ALTERNATIVE.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES & EQUIPMENT. ALL APPLIANCES & EQUIPMENT
 SHALL BE LISTED PER THE 2010 FBC-R SEC.G2404.3.
 3)THE FOLLOWING ITEMS SHALL BE IDENTIFIED ON BOTH
 DRAWINGS FOR THE INSTALLATION OF THE GAS PIPING UNDER
 THE BUILDING SLAB IF IT IS ALLOWED. THE INSTALLATION
 UNDER THE SALB IS CONTINGENT UPON THE LOCATION OF THE
 GAS DRYERS.
 A) INDICATE THE TYPE OF SLEEVE MATERIAL FOR THE PIPING
 FOR THE DRYERS ON THE PLAN. THE MATERIAL SHALL COMPLY
 WITH 2010 FBC-R SEC.G2415.12.
 B) THE TERMINATION OF THE CONDUIT INDOOR AND OUTDOOR
 SHALL COMPLY WITH 2010 FBC-R SEC. G2415.12.1.
 C) INDICATE ON THE PLAN HOW THE ANNULAR SPACE BETWEEN
 THE GAS PIPING AND THE SLEEVE IS TO BE SEALED. BE
 SPECIFIC.
 D) INDICATE THE TYPE OF GAS PIPING TO BE INSTALLED TO
 THE DRYERS. PE PIPING CAN ONLY BE INSTALLED OUTSIDE
 UNDERGROUND PER THE 2010 FBC-R SEC. G2415.15.1.
 4) INDICATE THE APPLICABLE SIZING TABLES USED FOR THE
 SIZING OF THE PE LINE AND ALSO THE PIPING TO THE
 DRYERS.2010 FBC-R SEC. G2413.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE 2
 PSI REGULATORS. REGULATORS SHALL COMPLY WITH 2010 FBC-R
 SEC.G2421.1 & G2421.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  