Plan Review Notes
Plan Review Notes For Permit 15061068
Permit Number 15061068
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-22 18:52:15PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.6, REQUIRES THE EACH SIGN HAVE A DISCONNECT.
 2. NEC 600.6(A) REQUIRES THAT THE DISCONNECT BE WITHIN
 SIGHT OF THE SIGN.
 3. NEC ARTICLE 600 HAS SPECIFIC ELECTRICAL REQUIREMENTS
 FOR SIGNS.
 4. FBC-E 505 HAS SPECIFIC SWITCHING REQUIREMENTS FOR
 SIGNS.
  
 ALL OF THE ABOVE SHALL BE COMPLIED WITH AND REFLECTED
 ON THE ELECTRICAL PAGE FOR THIS PERMIT APPLICATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  