Plan Review Notes For Permit 15061032 |
Permit Number |
15061032 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-24 16:37:49 | 6/24/2015 | | PROJECT: TROLLEY SHELTER 1 | | PERMIT#: 15061032 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS: | | | | 1) PROVIDE MANUFACTURER SPECS ON THE SOLAR PANEL AND | | LIGHT FIXTURES IN COMPLIANCE WITH NEC 110.3 AND NEC | | 690. | | | | 2) PROVIDE PLANS DETAILS FOR THE ELECTRICAL CONNECTIONS | | AND GROUNDING FOR THE SOLAR PANELS AND LIGHT FIXTURES. | | NEC 690, 300 AND 250 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|