| PROJECT: ORBIT LABS |
| PERMIT#: 15061012 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) NEC 230.2 |
| A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| BY ONLY ONE SERVICE. PROVIDE REVISED ELECTRICAL RISER |
| DIAGRAM FOR ONE SERVICE THAT SUPPORTS THE TOTAL |
| CONNECTED LOAD OF THE ENTIRE BUILDING. |
| |
| 2) NEC 225.34 (A) |
| THE TWO TO SIX DISCONNECTS AS PERMITTED IN 225.33 SHALL |
| BE GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| THE LOAD SERVED. |
| |
| 3) NEC 220.16 |
| PROVIDE A COMPLETE ELECTRICAL LOAD SUMMARY CALCULATION. |
| |
| 4) NEC 110.16. |
| PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| |
| 5) NEC 110.9 |
| VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. |
| |
| 6) WPB AMENDMENTS TO FBC 107.2.1 |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 7) WPB AMENDMENTS TO FBC 107.2.1.4 |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |